Inspections for the day of: Friday, December 21, 2001.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00526 INSP-Alarm Testing12/21/200112/21/200112/21/2001 12:00:00 AM PASS
FIR01-00605 INSP-Sprinkler Rough-in/Hydro12/20/200112/21/200112/21/2001 12:00:00 AMAPART
Ok to cover after removing concrete on riser ell down to expose bolts and hard cover protection of supply connection (potential contamination).
BLD01-02028 FIRE-Final Inspection12/19/200112/21/200112/21/2001 12:00:00 AMACANC
JIM ###-####
BLD01-02900 FIRE-Final Inspection12/20/200112/21/200112/21/2001 12:00:00 AMAPASS
###-####
BLD00-02647 FIRE-Final Inspection12/20/200112/21/200112/21/2001 12:00:00 AMAPASS
###-####
FIR01-00021 INSP-Alarm Testing12/21/200112/21/200112/21/2001 12:00:00 AMAFAIL
Scheduled by Inspector: 409 On 12/21/2001 4:32:44 AM preaction system not working; c/n issued for ther items 12/24/2001 5:54:14 AM
FIR01-00603 INSP-Alarm Testing12/21/200112/21/200112/21/2001 12:00:00 AMPPASS
david ###-####
BLD01-02133 FIRE-Final Inspection12/21/200112/21/200112/21/2001 12:00:00 AMPPASS
###-####
BLD01-02462 FIRE-Final Inspection12/21/200112/21/200112/21/2001 12:00:00 AMPCANC
###-####-----------------------cancel per dennis
BLD01-02742 FIRE-Final Inspection12/20/200112/21/200112/21/2001 12:00:00 AMPNR
###-#### per telephone call from Carl Dep. the door hardware is wrong; need extinguisher. They will call to reschedule 12/21/2001 12:27:56 PM
BLD01-01690 FIRE-Final Inspection12/20/200112/21/200112/21/2001 12:00:00 AMPPASS
Needed "K" extinguisher (trade out in Kitchen). Mike @ General Fire will comply (verbal). Called Owners Rep (Tracy Weir) that the portable skillet (in a box on the counter) will not be allowed in this facility or aType 1 Hood will be required. She said she would remove it and comply! ###-####
BLD01-02771 FIRE-Final Inspection12/21/200112/21/200112/21/2001 12:00:00 AMPFAIL
Scheduled by Inspector: 409 On 12/21/2001 2:03:31 PM need lobby door hardware and closure; alarms tested okay; 12/21/2001 2:08:01 PM
FIR01-00603 INSP-Final Inspection12/21/200112/21/200112/21/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 12/21/2001 2:06:19 PM
BLD01-02028 FIRE-Final Inspection12/19/200112/21/200112/21/2001 12:00:00 AMPNR
JIM ###-#### will reschedule 12/21/2001 2:02:00 PM