Inspections for the day of: Wednesday, December 21, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03804 ELE-Aging Inspection12/21/200512/21/200512/22/2005 9:54:17 AM DONE
see final
ELE04-03805 ELE-Aging Inspection12/21/200512/21/200512/22/2005 9:43:38 AM FAIL
see final
ELE05-03707 Final12/21/200512/21/200512/21/2005 4:11:25 PMPPASS
jeremiah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, check out 2 fixtures, elev not done, no card signed, ok to final elect only
ELE05-01293 Final12/21/200512/21/200512/21/2005 4:09:57 PMPPASS
jeremiah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles elev not done, no card signed, elect only ok to final
ELE05-02923 Final12/21/200512/21/200512/21/2005 3:49:39 PMPFAIL
sean kelley; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called cont, all but 1 recpt show open gnd
ELE05-04514 Electrical Rough-In12/21/200512/21/200512/21/2005 3:48:37 PMPFAIL
uffer ground- four star elec; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, not 2" of concrete around electrode
ELE04-04022 Final12/21/200512/21/200512/21/2005 2:14:12 PMPPASS
Scheduled by a contractor via Hello! on 12/21/2005 at 8:25:34 AM. Contact: ###-####. signed occ card, ok to final
ELE05-04571 Electrical Rough-In12/21/200512/21/200512/21/2005 12:26:58 PMPFAIL
###-#### - spencer called, left message, left corr notice,210.52(A) recpts shall be added in lr and mbr for 6' along floor line, 334.30 nm cable shall be stapled within 12" of panel,BCC address, job id sahll be posted, shall see u/g to garage
ELE05-04564 Electrical Rough-In12/20/200512/21/200512/21/2005 9:45:41 AMAPASS
call for access///mike ###-#### ric ok, check panel at final
ELE05-04560 Temporary Service12/20/200512/21/200512/21/2005 9:44:23 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, left corr notice, 250.66 gec shall be min #6, 590.6 recpt shall be gfci, 590.6(B)(1) 50a recpts shall be gfci, 406.8(B)(1),(2) recpts shall have in-use covers
ELE05-04553 Final12/20/200512/21/200512/21/2005 8:52:16 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE05-03467 Electrical Rough-In12/20/200512/21/200512/21/2005 8:51:50 AMAPART
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to cover rear outside wall for a/c
ELE05-04559 Electrical Rough-In12/20/200512/21/200512/21/2005 8:08:02 AMAPART
Scheduled by a contractor via Hello! on 12/20/2005 at 1:06:55 PM. Contact: ###-####. rear walls only ok to cover
ELE05-04563 Final12/20/200512/21/200512/21/2005 8:07:11 AMANR
###-#### jessie need rear outside light. said to reschedule