ELE04-03804
| ELE-Aging Inspection | 12/21/2005 | 12/21/2005 | 12/22/2005 9:54:17 AM | | DONE |
|
|
see final
|
ELE04-03805
| ELE-Aging Inspection | 12/21/2005 | 12/21/2005 | 12/22/2005 9:43:38 AM | | FAIL |
|
|
see final
|
ELE05-03707
| Final | 12/21/2005 | 12/21/2005 | 12/21/2005 4:11:25 PM | P | PASS |
|
|
jeremiah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, check out 2 fixtures, elev not done, no card signed, ok to final elect only
|
ELE05-01293
| Final | 12/21/2005 | 12/21/2005 | 12/21/2005 4:09:57 PM | P | PASS |
|
|
jeremiah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles elev not done, no card signed, elect only ok to final
|
ELE05-02923
| Final | 12/21/2005 | 12/21/2005 | 12/21/2005 3:49:39 PM | P | FAIL |
|
|
sean kelley; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called cont, all but 1 recpt show open gnd
|
ELE05-04514
| Electrical Rough-In | 12/21/2005 | 12/21/2005 | 12/21/2005 3:48:37 PM | P | FAIL |
|
|
uffer ground- four star elec; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, not 2" of concrete around electrode
|
ELE04-04022
| Final | 12/21/2005 | 12/21/2005 | 12/21/2005 2:14:12 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/21/2005 at 8:25:34 AM. Contact: ###-####. signed occ card, ok to final
|
ELE05-04571
| Electrical Rough-In | 12/21/2005 | 12/21/2005 | 12/21/2005 12:26:58 PM | P | FAIL |
|
|
###-#### - spencer called, left message, left corr notice,210.52(A) recpts shall be added in lr and mbr for 6' along floor line, 334.30 nm cable shall be stapled within 12" of panel,BCC address, job id sahll be posted, shall see u/g to garage
|
ELE05-04564
| Electrical Rough-In | 12/20/2005 | 12/21/2005 | 12/21/2005 9:45:41 AM | A | PASS |
|
|
call for access///mike ###-#### ric ok, check panel at final
|
ELE05-04560
| Temporary Service | 12/20/2005 | 12/21/2005 | 12/21/2005 9:44:23 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, left corr notice, 250.66 gec shall be min #6, 590.6 recpt shall be gfci, 590.6(B)(1) 50a recpts shall be gfci, 406.8(B)(1),(2) recpts shall have in-use covers
|
ELE05-04553
| Final | 12/20/2005 | 12/21/2005 | 12/21/2005 8:52:16 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
|
ELE05-03467
| Electrical Rough-In | 12/20/2005 | 12/21/2005 | 12/21/2005 8:51:50 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to cover rear outside wall for a/c
|
ELE05-04559
| Electrical Rough-In | 12/20/2005 | 12/21/2005 | 12/21/2005 8:08:02 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 12/20/2005 at 1:06:55 PM. Contact: ###-####. rear walls only ok to cover
|
ELE05-04563
| Final | 12/20/2005 | 12/21/2005 | 12/21/2005 8:07:11 AM | A | NR |
|
|
###-#### jessie need rear outside light. said to reschedule
|