Inspections for the day of: Wednesday, December 21, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00684 INSP-Sprinkler Rough-in12/21/200512/21/200512/22/2005 8:18:06 AMPDEFR
Inspection to be completed 12/ 22 per agreement with contractor.
BLD05-02928 FIRE-Final Inspection12/20/200512/21/200512/21/2005 5:04:40 PMPFAIL
Repair exit sign at south exit corridor; existing access controlled egress door must meet requirements of IFC 2003 1008.1.3.4.. See correction notice for details.
BLD05-02927 FIRE-Final Inspection12/20/200512/21/200512/21/2005 5:00:21 PMPFAIL
Repair exit sign; failed to function on battery backup. Remaining items satisfactory.
BLD05-00011 FIRE-Final Inspection12/20/200512/21/200512/21/2005 3:24:08 PMACANC
Per contractor the fire alarm is not ready for final inspection, life safety cannot be approved prior to alarm final.
FIR05-00595 INSP-Final Inspection12/20/200512/21/200512/21/2005 3:22:33 PMANR
Per contractor job is not ready for inspection, work is incomplete.
FIR05-00618 INSP-Final Inspection12/20/200512/21/200512/21/2005 3:21:23 PMANR
Per contractor job is not ready for inspection, work is incomplete.
FIR05-00754 INSP-Final Inspection12/20/200512/21/200512/21/2005 3:10:26 PMAFAIL
Two dampers failed to close upon smoke detection, strobe in the new office is not in sync with the remainder of the floor strobes, discussed this situation with the contractor for pending remodel on this floor.
FIR05-00236 INSP-Final Inspection12/20/200512/21/200512/21/2005 3:06:02 PMAFAIL
Strobe in the staff break room is blocked by a wall not shown on plans, coverage in this area is incomplete, relocate or add an additional device, all other items tested okay.
FIR05-00676 INSP-Alarm Testing12/20/200512/21/200512/21/2005 11:09:08 AMAFAIL
A door has been added from the assembly area to the storage room disrupting the occupancy separation, this area will now require connection to the voice evac. and visual notification as well. No inspection until plans have been resubmitted and approved with required changes reflecting correct floor plan as installed.
FIR05-00493 INSP-Final Inspection12/20/200512/21/200512/21/2005 10:26:52 AMAPASS
Required correction has been completed, fire sprinkler permit finaled.
FIR05-00746 INSP-Sprinkler Rough-in/Hydro12/20/200512/21/200512/21/2005 9:50:36 AMAPART
Rough-in at vending, excersise, guest laundry, kitchen and corridor are acceptable to cover, two locations at service laundry are overspaced-see approved plans for locations.