FIR06-00891
| INSP-Alarm Testing | 12/21/2006 | 12/21/2006 | 12/21/2006 4:39:13 PM | P | FAIL |
|
|
Mike Timmerman and I stopped at this project three times today. Mike performed the inspection. Per Mike the only items tested were the a/v's. Many of these had the wrong candella settings. The fire alarm panel installed is not what was approved. Per Mike there are also many changes. The fire alarm contractor will be required to resubmit drawings prior to any more inspections.
|
FIR06-00548
| INSP-Sprinkler Rough-in/Hydro | 12/21/2006 | 12/21/2006 | 12/21/2006 4:34:47 PM | P | PASS |
|
|
The overhead hydro test passed.
|
BLD06-00907
| FIRE-Final Inspection | 12/21/2006 | 12/21/2006 | 12/21/2006 4:32:54 PM | P | FAIL |
|
|
Provide indicator at the main exit, lower fire extinguishers as discussed and repair the two north most exit signs.
|
BLD06-02180
| FIRE-Final Inspection | 12/20/2006 | 12/21/2006 | 12/21/2006 3:13:31 PM | P | FAIL |
|
|
Lower fire extinguishers, provide the correct remote annunciator for the duct smoke detector and the correct sample tube.
|
BLD06-00710
| FIRE-Final Inspection | 12/21/2006 | 12/21/2006 | 12/21/2006 1:13:40 PM | P | FAIL |
|
|
Smoke detector in 5265 at the top of the stairs does not operate correctly. All other items are ok
|
FIR06-00075
| INSP-Sprinkler Rough-in | 12/20/2006 | 12/21/2006 | 12/21/2006 12:59:44 PM | A | PASS |
|
|
Permit finaled
|
FIR06-00597
| INSP-Sprinkler Rough-in | 12/20/2006 | 12/21/2006 | 12/21/2006 12:31:57 PM | A | PASS |
|
|
sprinkler piping is ok to cover. as-builts are needed showing the additional heads
|
MIS06-00338
| FIR-Final | 12/20/2006 | 12/21/2006 | 12/21/2006 12:19:38 PM | A | PART |
|
|
A temporary occupancy was given until the fire extinguisher at the front exit is tagged, the missing sprinkler canopies are replaced and the exit signs and emergency light are repaired and tested.
|
FIR06-00955
| INSP-Sprinkler Rough-in | 12/20/2006 | 12/21/2006 | 12/21/2006 11:30:08 AM | A | PART |
|
|
Sprinkler piping is ok to cover but some items have not been corrected. See city approved plans for the redlined items.
|
FIR06-00491
| INSP-Alarm Testing | 12/20/2006 | 12/21/2006 | 12/21/2006 10:37:12 AM | P | CANC |
|
|
jason/mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Patricia Smith
|
FIR06-00850
| INSP-Final Inspection | 12/21/2006 | 12/21/2006 | 12/21/2006 10:22:01 AM | P | PASS |
|
|
permit finaled
|
BLD06-00710
| FIRE-Final Inspection | 12/20/2006 | 12/21/2006 | 12/21/2006 10:07:03 AM | A | FAIL |
|
|
Provide fire extinguishers and test the smoke alarms and door closure in the two center units.
|
FIR06-00900
| INSP-Sprinkler Rough-in/Hydro | 12/20/2006 | 12/21/2006 | 12/21/2006 9:25:08 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD06-03193
| FIRE-Final Inspection | 12/20/2006 | 12/21/2006 | 12/21/2006 9:24:26 AM | A | FAIL |
|
|
Provide keyed hardware for the egress side of the main entry door and remove the thumbturn, Tag the new fire extinguishers. Verify the exit lights have all been repaired.
|
FIR06-00891
| INSP-Final Inspection | 12/20/2006 | 12/21/2006 | 12/21/2006 8:34:12 AM | P | CANC |
|
|
Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|