Inspections for the day of: Thursday, December 21, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00891 INSP-Alarm Testing12/21/200612/21/200612/21/2006 4:39:13 PMPFAIL
Mike Timmerman and I stopped at this project three times today. Mike performed the inspection. Per Mike the only items tested were the a/v's. Many of these had the wrong candella settings. The fire alarm panel installed is not what was approved. Per Mike there are also many changes. The fire alarm contractor will be required to resubmit drawings prior to any more inspections.
FIR06-00548 INSP-Sprinkler Rough-in/Hydro12/21/200612/21/200612/21/2006 4:34:47 PMPPASS
The overhead hydro test passed.
BLD06-00907 FIRE-Final Inspection12/21/200612/21/200612/21/2006 4:32:54 PMPFAIL
Provide indicator at the main exit, lower fire extinguishers as discussed and repair the two north most exit signs.
BLD06-02180 FIRE-Final Inspection12/20/200612/21/200612/21/2006 3:13:31 PMPFAIL
Lower fire extinguishers, provide the correct remote annunciator for the duct smoke detector and the correct sample tube.
BLD06-00710 FIRE-Final Inspection12/21/200612/21/200612/21/2006 1:13:40 PMPFAIL
Smoke detector in 5265 at the top of the stairs does not operate correctly. All other items are ok
FIR06-00075 INSP-Sprinkler Rough-in12/20/200612/21/200612/21/2006 12:59:44 PMAPASS
Permit finaled
FIR06-00597 INSP-Sprinkler Rough-in12/20/200612/21/200612/21/2006 12:31:57 PMAPASS
sprinkler piping is ok to cover. as-builts are needed showing the additional heads
MIS06-00338 FIR-Final12/20/200612/21/200612/21/2006 12:19:38 PMAPART
A temporary occupancy was given until the fire extinguisher at the front exit is tagged, the missing sprinkler canopies are replaced and the exit signs and emergency light are repaired and tested.
FIR06-00955 INSP-Sprinkler Rough-in12/20/200612/21/200612/21/2006 11:30:08 AMAPART
Sprinkler piping is ok to cover but some items have not been corrected. See city approved plans for the redlined items.
FIR06-00491 INSP-Alarm Testing12/20/200612/21/200612/21/2006 10:37:12 AMPCANC
jason/mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Patricia Smith
FIR06-00850 INSP-Final Inspection12/21/200612/21/200612/21/2006 10:22:01 AMPPASS
permit finaled
BLD06-00710 FIRE-Final Inspection12/20/200612/21/200612/21/2006 10:07:03 AMAFAIL
Provide fire extinguishers and test the smoke alarms and door closure in the two center units.
FIR06-00900 INSP-Sprinkler Rough-in/Hydro12/20/200612/21/200612/21/2006 9:25:08 AMAPASS
Sprinkler piping is ok to cover
BLD06-03193 FIRE-Final Inspection12/20/200612/21/200612/21/2006 9:24:26 AMAFAIL
Provide keyed hardware for the egress side of the main entry door and remove the thumbturn, Tag the new fire extinguishers. Verify the exit lights have all been repaired.
FIR06-00891 INSP-Final Inspection12/20/200612/21/200612/21/2006 8:34:12 AMPCANC
Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley