Inspections for the day of: Friday, December 21, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03652 Final12/21/200712/21/200712/21/2007 4:04:14 PMPPASS
Scheduled by a contractor via Hello! on 12/21/2007 at 10:39:09 AM. Contact: ###-####. ok to final, signed structural card
ELE07-03653 Final12/21/200712/21/200712/21/2007 3:32:10 PMPPASS
Scheduled by a contractor via Hello! on 12/21/2007 at 10:38:16 AM. Contact: ###-####. ok to final, signed structural card
ELE07-00396 Final12/21/200712/21/200712/21/2007 2:58:18 PMPPASS
jim Phone #: ###-#### met electricians, corrections made, ok to final
ELE07-03565 Final12/21/200712/21/200712/21/2007 2:17:52 PMPPASS
hz Phone #: ###-#### ok to final
ELE07-04194 Temporary Service12/21/200712/21/200712/21/2007 1:32:22 PMPPASS
Scheduled by a contractor via Hello! on 12/21/2007 at 9:33:01 AM. Contact: ###-####. called contr, t/s o/h n ok
ELE07-01624 Electrical Rough-In12/21/200712/21/200712/21/2007 12:55:04 PMPPASS
steve Phone #: ###-#### ok to cover west stairwell
ELE07-03241 Final12/20/200712/21/200712/21/2007 11:13:04 AMAPASS
We have made the nessary corrections Phone #: ###-#### Internet Inspection Request from: Scott Abbott corrections made, signed occupancy card, ok to final
ELE07-03867 Conference12/20/200712/21/200712/21/2007 10:27:06 AMADONE
Alejandro ###-#### please call when on way homeowner not sure there will be any wiring required, told that if any wiring done or exposed we need to do ri inspection before cover
ELE07-04188 Rough-In Permanent Service12/20/200712/21/200712/21/2007 10:07:40 AMAFAIL
Scheduled by a contractor via Hello! on 12/20/2007 at 3:22:40 PM. Contact: ###-####. called contractor, left correction notice, nec 334.30(A) rmc shall be securely fastened within 3' of service head for above roof termination of mast, 352.30(A) rnc shall be secured within 3' of grade, 352.30(B) rnc shall be strapped every 5', 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members
ELE07-04188 Electrical Rough-In12/21/200712/21/200712/21/2007 10:01:24 AMAPASS
Scheduled by a contractor via Hello! on 12/20/2007 at 3:22:40 PM. Contact: ###-####. called contr about nail plates, ric ok
ELE07-04185 Permanent Service12/20/200712/21/200712/21/2007 9:30:04 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Steve Craig p/s o/h rec ok
ELE07-04181 Electrical Rough-In12/20/200712/21/200712/21/2007 9:12:33 AMAPASS
richard - uffer Phone #: ###-#### ok to backfill concrete encased electrode
ELE07-03785 Electrical Rough-In12/20/200712/21/200712/21/2007 8:44:34 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamiltonnnnok to cover ceiling anop
ELE07-04187 Final12/20/200712/21/200712/21/2007 8:31:36 AMAPASS
steve Phone #: ###-#### called contractor, ok to final
ELE07-04147 Final12/20/200712/21/200712/20/2007 12:38:22 PMACANC
electrician is Nick Felsted Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer Inspection cancelled from web by: gary batten