Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00945 FIRE-Final Inspection12/21/200912/21/200912/21/2009 6:07:40 PMPPART
Items at "phase 5" repaired while on site include EM lights, door hardware at two locations, one exit sign. Mag lock at the north exit disabled, notified contractor hardware must comply with IFC chapter 10 if functional.
FIR09-00626 INSP-Final Inspection12/21/200912/21/200912/21/2009 6:03:43 PMPPASS
Fire sprinkler permit work finaled.
FIR09-00622 INSP-Final Inspection12/18/200912/21/200912/21/2009 6:03:08 PMAFAIL
Missing one notification appliance at the warehouse Area C, one cd setting at the ramp is incorrect, need access to the laundry room and company store for functional testing, notification at some areas including the tool crib and mixing room appears to be obstructed, non-functional existing FA system devices to be removed. Two duct detectors at area C warehouse passed testing.
BLD09-01028 FIRE-Final Inspection12/18/200912/21/200912/21/2009 5:54:18 PMAPASS
Items on the previous correction notice are finished, noted missing building address numbers to be posted prior to final structrual approval.
BLD09-02123 FIRE-Final Inspection12/18/200912/21/200912/21/2009 5:52:02 PMAFAIL
Missing ceiling tile and escutcheon at the closet adjacent to the main entry, need verification that the mag lock at the main entry/exit is tied in to the fire alarm system (also missing "push to exit button").