Inspections for the day of: Tuesday, December 21, 2010.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02077 ELE-Aging Inspection12/21/201012/21/201012/28/2010 12:44:35 PM CANC
see added final
ELE10-01563 ELE-Aging Inspection12/21/201012/21/201012/27/2010 10:14:08 AM DONE
see added final
ELE09-02140 ELE-Aging Inspection12/21/201012/21/201012/27/2010 9:52:52 AM DONE
wsuc
ELE10-02811 Final12/21/201012/21/201012/21/2010 3:19:03 PMPPASS
Gene Phone #: ###-####
ELE10-02790 Permanent Service12/21/201012/21/201012/21/2010 3:18:34 PMPFAIL
Jared Phone #: ###-#### >> Inspection requested via web by joel smith
called violation not corrected
ELE10-02824 Electrical Rough-In12/21/201012/21/201012/21/2010 3:17:36 PMPPART
ground work Roughin, Concrete Pad to be poured today @ 3:00pm Phone #: ###-#### >> Inspection requested via web by David Oliver u/g for slab ok still needs 18" for other area
ELE10-02785 Final12/21/201012/21/201012/21/2010 2:31:25 PMPFAIL
Code Corrections Made - Cleaned busing, changed transformer from 208 to 240 Phone #: ###-#### >> Inspection requested via web by Todd Alder called corr. posted grd both high and low voltage services 250.20, 24, 30 230.2 plaques for 480 and 120/240 services, 210.5(C) id branch circuits of both systems
ELE10-02207 Final12/21/201012/21/201012/21/2010 2:27:31 PMPPASS
Final on bathroom addition on west end of building. Construction access is off of supply way. I will be on site and would like to ask some question so please call. ###-#### Phone #: ###-#### >> Inspection requested via web by Lynn Cable
ok card signed
ELE10-01638 Electrical Rough-In12/20/201012/21/201012/21/2010 12:09:59 PMAPASS
david Phone #: ###-####
ELE10-01190 Electrical Rough-In12/20/201012/21/201012/21/2010 12:09:44 PMANR
ivan Phone #: ###-####
ELE10-01190 Conference12/21/201012/21/201012/21/2010 12:09:33 PMADONE
ivan Phone #: ###-#### went over NEC with owner
ELE10-02399 Final12/20/201012/21/201012/21/2010 12:08:41 PMAPASS
stan - please call 1/2 hr prior Phone #: ###-#### ok card signed
ELE10-02786 Rough-In Permanent Service12/20/201012/21/201012/21/2010 12:08:16 PMAPASS
this job is ready for inspection Monday 12/20/10 if you have time.

Thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe r/i p/s u/g new ok
ELE10-02787 Rough-In Permanent Service12/20/201012/21/201012/21/2010 12:07:14 PMAPASS
this job is ready Monday 12/20/10 if you have time to do it. Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe r/i p/s u/g new ok
ELE10-00131 Final12/20/201012/21/201012/21/2010 12:06:45 PMAPASS
bud Phone #: ###-#### ok
ELE10-02180 Permanent Service12/20/201012/21/201012/21/2010 10:36:29 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Sean DeLacy
p/s u/g new ok
ELE10-01708 ELE-Aging Inspection12/21/201012/21/201012/21/2010 7:36:12 AM DONE
wsuc