Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS11-00321 FIR-Conference12/21/201112/21/201112/23/2011 11:56:18 AMPDONE
I spoke over the phone to Mike with Treasure Valley Hospital and he was going to check into a building permit. I notified Mike Jordan as well
FIR11-00464 INSP-Alarm Testing12/20/201112/21/201112/21/2011 2:39:06 PMPCANC
Cancel per contractors request.
FIR11-00464 INSP-Final Inspection12/20/201112/21/201112/21/2011 2:38:46 PMPCANC
Cancel per contractors request.
BLD11-02386 FIRE-Final Inspection12/21/201112/21/201112/21/2011 10:30:03 AMPPASS
life safety passed
FIR11-00661 INSP-Final Inspection12/20/201112/21/201112/21/2011 10:29:32 AMAPASS
permit finaled
BLD11-02864 FIRE-Final Inspection12/20/201112/21/201112/21/2011 10:22:48 AMAFAIL
Provide inspection and final sign off for the outstanding fire alarm permit FIR02-00290. (sentry security systems ###-####), Remove the thumbturn lock from the main exit and rear exit door. Provide sticker at the main exit door. provide one 2A, 10BC fire extinguisher with current inspection tag mounted in a normal path of travel no higher than 5', provide for annual inspection of the fire sprinkler system.
BLD11-01955 FIRE-Final Inspection12/21/201112/21/201112/21/2011 10:19:35 AMPPASS
life safety passed
BLD11-01955 FIRE-Final Inspection12/21/201112/21/201112/21/2011 10:19:14 AMPPASS
life safety passed
FIR11-00607 INSP-Sprinkler Rough-in/Hydro12/20/201112/21/201112/21/2011 10:18:29 AMAPASS
24 hour air test passed
FIR11-00607 INSP-Sprinkler Rough-in12/20/201112/21/201112/21/2011 10:18:07 AMAPASS
24 hour air test passed
FIR11-00626 INSP-Sprinkler Rough-in12/20/201112/21/201112/21/2011 10:17:37 AMAPASS
Sprinkler piping is ok to cover. Fire treated wood has been installed in limited quantities above the ceiling.
FIR11-00670 INSP-Final Inspection12/20/201112/21/201112/21/2011 10:03:45 AMAPASS
permit finaled
BLD11-02962 FIRE-Final Inspection12/20/201112/21/201112/21/2011 9:23:08 AMAFAIL
Repair or remove the exit sign and provide annual inspection for the fire extinguisher.
BLD11-02914 FIRE-Final Inspection12/20/201112/21/201112/21/2011 9:16:39 AMAPASS
life safety passed
BLD11-00923 FIRE-Final Inspection12/21/201112/21/201112/21/2011 9:07:59 AMPPASS
life safety passed
FIR11-00436 INSP-Final Inspection12/21/201112/21/201112/21/2011 8:47:00 AMAPASS
permit finaled
FIR11-00380 INSP-Final Inspection12/20/201112/21/201112/21/2011 8:46:34 AMAPASS
permit finaled
BLD11-02386 FIRE-Final Inspection12/20/201112/21/201112/20/2011 3:56:13 PMAFAIL
Life safety will be able to be finaled when the project related fire alarm is complete.