FIR15-00618
| INSP-Alarm Testing | 12/14/2015 | 12/21/2015 | 12/21/2015 3:08:31 PM | P | DONE |
|
|
As-builts are needed showing deleted devices, added devices and address changes. Verified battery size in panel and panel model. Verifed a/v's have been removed per the approved plans. I noted that the smoke detectors for door release will need to be centered on doors. The access controled egress doors will need to be connected to the fire alarm system per the IFC. Interior doors on hold opens need to release on alarm and when the panel becomes inactive as discussed.
|
FIR15-00513
| INSP-Alarm Testing | 12/14/2015 | 12/21/2015 | 12/21/2015 3:02:51 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Brian Richard
|