Inspections for the day of: Wednesday, December 21, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-04153 Final12/20/201612/21/201612/21/2016 4:10:17 PMPPASS
FINAL Phone #: ###-#### Inspection requested via web by Diane Day
MEC16-05010 Rough-in12/16/201612/21/201612/21/2016 3:33:47 PMPPASS
Rough In/Pressure Phone #: ###-#### Inspection requested via web by Diane Day- R/I ok
MEC16-05010 Pressure Test12/16/201612/21/201612/21/2016 3:33:24 PMPPASS
Rough In/Pressure Phone #: ###-#### Inspection requested via web by Diane Day- 20lb gas pass- 5lb flue pass
MEC16-04618 Rough-in12/20/201612/21/201612/21/2016 3:07:14 PMPPASS
Rough In Phone #: ###-#### Inspection requested via web by Diane Day
MEC16-05659 Final12/20/201612/21/201612/21/2016 2:41:56 PMPPASS
Inspection requested via web by Margie Rowe
MEC15-05385 Final12/21/201612/21/201612/21/2016 1:33:39 PMPFAIL
need combustion air in water heater closet- need 1" clearancve to combustibles to b vent on water heater flue- need foilmtape removed from b vent- need uv protection on line sets outdoors- need tp rodent proof penetrations exterior of building and seal off- left correction notice in closet by water heater
MEC16-05680 Final12/21/201612/21/201612/21/2016 11:34:48 AMAPASS
MEC16-05680 Final12/20/201612/21/201612/21/2016 9:57:08 AMAFAIL
OWNER GLADYS DURFEY ###-#### Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING- need right size fuses in disconnect at A/C outside- reinspection needed
MEC16-04963 Final12/20/201612/21/201612/21/2016 9:29:21 AMAPART
partial final inspection Phone #: ###-#### Inspection requested via web by Nicholas Paige- elbows need insulated at entry way- rest looks ok- ok to install ceiling tiles after all trades are complete with inspections
MEC16-05615 Final12/16/201612/21/201612/20/2016 4:18:32 PMAPASS
Please call the Tenant, Jennifer at ###-#### with a 30 minute heads up arrival time. Phone #: ###-#### Inspection requested via web by David or K Cole