Inspections for the day of: Wednesday, December 21, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04086 Permanent Service12/21/201612/21/201612/21/2016 2:08:32 PMPPASS
Ralph Horsley-electrician Phone #: ###-#### Inspection requested via web by Kenneth R. Horsley...

p/s u/g n ok
ELE15-02845 Conference12/21/201612/21/201612/21/2016 1:47:32 PMPDONE
Shawn Phone #: ###-####...

discussed service change options...recommended hiring electrician for job...
ELE16-03372 Final12/20/201612/21/201612/21/2016 12:55:16 PMPPASS
Final (forgot phone number on last request) Phone #: ###-#### Inspection requested via web by Lynn Laurel....

ok to final
ELE16-04084 Electrical Rough-In12/21/201612/21/201612/21/2016 12:17:48 PMPPASS
Front door key is under mat. dead bolt is the only one that works. Phone #: ###-#### Inspection requested via web by Jerry Moore...

rough ok to cover....added 2 outlets dining east wall, reconfigure kit new location, added entry light
ELE16-02846 Final12/16/201612/21/201612/21/2016 10:41:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot...

1) lock outs need applied to overcurrent protection of hard wired appliances
2) disposal oulet must be readily accessible
3) panel shall be labelled clear and legible to specify specific circuit
4) A/C disconnects and over current device shall be labelled for each seperate A/C
5) overcurrent device for A/C is to large
6) outlets serving master bath sinks cannot be enclosed in cabinets...210.52(D)
7) future 50A circuit shall have GFI protection either in panel or at disconnect
ELE16-01961 Electrical Rough-In12/20/201612/21/201612/21/2016 8:58:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...

ok cover...mech rm understair wall
ELE13-02945 Final12/20/201612/21/201612/21/2016 8:28:01 AMAPASS
Matt Phone #: ###-####...

corrections made ok to final
ELE16-03372 Final12/20/201612/21/201612/20/2016 2:57:39 PMPCANC
final >> Inspection requested via web by Lynn Laurel Inspection cancelled from web by: Lynn Laurel
ELE16-04071 Rough-In Permanent Service12/20/201612/21/201612/20/2016 10:36:47 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Greg Traudt Inspection cancelled from web by: Greg Traudt