Inspections for the day of: Wednesday, December 21, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00088 INSP-Sprinkler Rough-in12/20/201612/21/201612/21/2016 2:14:24 PMPDONE
Request was for a conference, discussed tenting options with project superintendent to keep insulation on top of piping, also to maintain open space pocket between piping and vapor barrier/sheetrock for radiant heat to reach the piping.
FIR16-00188 INSP-Final Inspection12/20/201612/21/201612/21/2016 1:15:40 PMPPASS
Final fire sprinkler inspection passed/complete
FIR15-00182 INSP-Final Inspection12/21/201612/21/201612/21/2016 1:15:19 PMPPASS
Final underground inspection passed/complete
BLD15-02600 FIRE-Final Inspection12/21/201612/21/201612/21/2016 1:13:38 PMAPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags, premise has a knox box. Final life fire safety inspection passed/complete.
FIR08-00368 FIR-Aging Inspection12/21/201612/21/201612/21/2016 12:36:52 PM CANC
FIR15-00182 INSP-Supply line flush12/20/201612/21/201612/21/2016 12:18:21 PMPDONE
Underground main line flush complete
FIR16-00223 INSP-Supply line flush12/21/201612/21/201612/21/2016 12:16:30 PMPDONE
Underground main line flush complete
FIR16-00573 INSP-Sprinkler Rough-in12/20/201612/21/201612/21/2016 9:08:59 AMAPASS
Overhead fire sprinkler pipe tenting complete for piping located in attic spaces, piping in attic spaces approved for cover. Material used for tenting is clear plastic sheeting to cover pipe, blow in insulation will be applied at a later date after sheetrock is installed, prefered method for tenting is batting type insulation to help insure R38 stays over the top of fire sprinkler piping and to maintain the clear pocket between the piping and the sheetrock for radiant heat.