ELE17-03984
| Electrical Rough-In | 12/20/2017 | 12/21/2017 | 12/21/2017 3:01:50 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer 3 walls marked on contractor print will be left open due to meeting rooms will require floor receptacles as per NEC 210.71. 2 meeting rooms large enough needed 2 floor receptacles. Will call for inspection for these 3 walls when ready. Rest of walls and hard lids rough in ok cover.
|
ELE17-04287
| Temporary Service | 12/21/2017 | 12/21/2017 | 12/21/2017 12:58:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|
ELE17-04245
| Temporary Service | 12/21/2017 | 12/21/2017 | 12/21/2017 11:30:31 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
|
ELE17-04170
| Permanent Service | 12/21/2017 | 12/21/2017 | 12/21/2017 11:28:42 AM | P | PASS |
|
|
William-as early as poss Phone #: ###-#### p/s o/h rec ok
|
ELE17-01337
| Electrical Rough-In | 12/20/2017 | 12/21/2017 | 12/21/2017 11:03:55 AM | A | PART |
|
|
We are requesting wall rough-in inspections for pool/spa area, fitness area, market place, kitchen and 2nd and 3rd floor electrical rooms for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Market place, kitchen areas not ready, Added level 4 units 401 thru 411 drop lids, level 2 and 3 electrical rooms, and walls in pool, spa, fitness areas rough in ok cover
|
ELE17-04245
| Temporary Service | 12/20/2017 | 12/21/2017 | 12/21/2017 9:32:44 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 250.64(B)- Where exposed, a grounding electrode conductor or its enclosure shall be securely fastened to the surface on which it is carried. Ground rod is 15' to southwest of temp pole.
|
ELE17-04204
| Final | 12/20/2017 | 12/21/2017 | 12/21/2017 8:57:04 AM | A | PASS |
|
|
Ben Phone #: ###-#### Final ok
|