Inspections for the day of: Thursday, December 21, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03984 Electrical Rough-In12/20/201712/21/201712/21/2017 3:01:50 PMPPART
Phone #: ###-#### Inspection requested via web by ron spen cer
3 walls marked on contractor print will be left open due to meeting rooms will require floor receptacles as per NEC 210.71. 2 meeting rooms large enough needed 2 floor receptacles. Will call for inspection for these 3 walls when ready. Rest of walls and hard lids rough in ok cover.
ELE17-04287 Temporary Service12/21/201712/21/201712/21/2017 12:58:12 PMPPASS
Phone #: ###-#### Inspection requested via web by David Nelson
t/s u/g n ok
ELE17-04245 Temporary Service12/21/201712/21/201712/21/2017 11:30:31 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
ELE17-04170 Permanent Service12/21/201712/21/201712/21/2017 11:28:42 AMPPASS
William-as early as poss Phone #: ###-#### p/s o/h rec ok
ELE17-01337 Electrical Rough-In12/20/201712/21/201712/21/2017 11:03:55 AMAPART
We are requesting wall rough-in inspections for pool/spa area, fitness area, market place, kitchen and 2nd and 3rd floor electrical rooms for tomorrow morning. Our contact is Rick @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Market place, kitchen areas not ready, Added level 4 units 401 thru 411 drop lids, level 2 and 3 electrical rooms, and walls in pool, spa, fitness areas rough in ok cover
ELE17-04245 Temporary Service12/20/201712/21/201712/21/2017 9:32:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
250.64(B)- Where exposed, a grounding electrode conductor or its enclosure shall be securely fastened to the surface on which it is carried. Ground rod is 15' to southwest of temp pole.
ELE17-04204 Final12/20/201712/21/201712/21/2017 8:57:04 AMAPASS
Ben Phone #: ###-####
Final ok