Inspections for the day of: Thursday, December 21, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-04353 FIRE-Final Inspection12/20/201712/21/201712/21/2017 1:52:32 PMPFAIL
Life safety will be ok to pass after the fire alarm modifications have been permited/passed. A notification device is required in the rear spa room (was a previous office)

Please call ahead for access - Marissa Phone #: ###-####
BLD17-00412 FIRE-Final Inspection12/20/201712/21/201712/21/2017 1:50:51 PMPFAIL
Door hardware issues, round knobs, thumb turn deadbolts have been used through out. Missing indicator and sticker at main exit. Missing exit sign and exit discharge light.

Butch Phone #: ###-####
BLD16-04311 FIRE-Final Inspection12/20/201712/21/201712/21/2017 1:49:09 PMPPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by David Scaggs
FIR17-00418 INSP-Final Inspection12/20/201712/21/201712/21/2017 12:19:23 PMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR17-00326 INSP-Final Inspection12/20/201712/21/201712/21/2017 12:18:42 PMPPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR16-00821 INSP-Sprinkler Rough-in/Hydro12/20/201712/21/201712/21/2017 11:47:27 AMPPASS
Overhead hydro test passed. Building 300 rough to cover passed. Piping can be covered.

Michael Phone #: ###-####
FIR17-00748 INSP-Sprinkler Rough-in12/21/201712/21/201712/21/2017 10:25:53 AMPCANC
Call Anthony before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR17-00631 INSP-Sprinkler Rough-in12/20/201712/21/201712/21/2017 9:38:42 AMPFAIL
Todays inspection was for the mezzanine in the back area. I had to fail it due to heads overspaced from the exterior wall, pipe size does not match plans and possible need for branchline restraints.

Contact Scott Powada - ###-####
BLD16-04312 FIRE-Final Inspection12/20/201712/21/201712/21/2017 8:52:07 AMPPASS
life safety passed

Phone #: ###-#### Inspection requested via web by David Scaggs
BLD16-04315 FIRE-Final Inspection12/20/201712/21/201712/21/2017 8:51:44 AMPPASS
Life safety passed

Phone #: ###-#### Inspection requested via web by David Scaggs
FIR17-00726 INSP-Supply line flush12/20/201712/21/201712/21/2017 8:43:35 AMACANC
Cancel per Brian Phone #: ###-####. To be rescheduled
BLD17-04367 FIRE-Final Inspection12/20/201712/21/201712/21/2017 8:09:40 AMAFAIL
Not ready for a final. Permits are required for the spinkler modifications and the smoke evac system needs to be modified for these two storage rooms and the exit corridor. I also noted that a fire extinguisher and door hardware needs to be installed

Troy Phone #: ###-####