ELE04-03903
| Final | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | A | PASS |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok 12/22/2004 8:16:30 AM
|
ELE04-03977
| Rough-In Permanent Service | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas r/i ok called outside light boxes shall be flush with siding
p/s u/g new ok 12/21/2004 2:50:19 PM
|
ELE04-04033
| Final | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | A | FAIL |
|
|
Permanent service for sign; Phone #: ###-#### Internet Inspection Request from: Rich Rice cor. posted called 250.24 terminate GEC to neutral bus, 344 bushing for rigid nipple, 358.42 use approved RT conn. and coup, 250.90&92 use meyers hub listed for bong and grd, 250.52(A)(2) grd steel pole 12/22/2004 9:34:35 AM
|
ELE04-03146
| Electrical Rough-In | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | A | PART |
|
|
Butch; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok 12/22/2004 10:13:18 AM
|
ELE04-03222
| Final | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | A | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 12/22/2004 8:46:37 AM
|
ELE04-03963
| Electrical Rough-In | 12/22/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | P | PART |
|
|
CONTACT: JOHN OSTALOSA; Phone #: ###-#### Internet Inspection Request from: Deb McCoy walls ok room #108 12/22/2004 1:13:16 PM
|
ELE04-03671
| Permanent Service | 12/22/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/22/2004 at 10:35:59 AM. Contact: ###-####. p/s u/g new ok 12/22/2004 12:28:17 PM
|
ELE04-03656
| Rough-In Permanent Service | 12/21/2004 | 12/22/2004 | 12/22/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/21/2004 at 1:41:33 PM. Contact: ###-####. r/i 4 units ok
p/s u/g new ok 12/22/2004 2:53:34 PM
|