BLD05-01911
| FIRE-Final Inspection | 12/22/2005 | 12/22/2005 | 12/23/2005 8:29:31 AM | P | PART |
|
|
###-#### Need to provide ADA approved hardware at the pocket door to the confrence room per IFC requirements, all other items tested okay.
|
BLD05-00978
| FIRE-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 4:35:04 PM | A | PART |
|
|
On site confrence to discuss requirements for use approval at the separate covered loading dock structure.
|
FIR05-00738
| INSP-Sprinkler Rough-in | 12/22/2005 | 12/22/2005 | 12/22/2005 3:41:09 PM | P | PART |
|
|
UG fire supply line is acceptable to cover.
|
MIS05-00218
| FIR-Final | 12/22/2005 | 12/22/2005 | 12/22/2005 3:21:01 PM | P | PASS |
|
|
All c/n items have been completed, life safety passed inspection.
|
BLD05-01668
| FIRE-Final Inspection | 12/22/2005 | 12/22/2005 | 12/22/2005 2:52:55 PM | P | PASS |
|
|
Life safety for vanilla finish is satisfactory.
|
MIS05-00136
| FIR-Final | 12/21/2005 | 12/22/2005 | 12/22/2005 2:45:55 PM | A | PASS |
|
|
Life safety is acceptable, existing hardware on the main entry/exit doors is satisfactory per building plan reviewer Ron Hill.
|
BLD05-00458
| BLD-Final | 12/22/2005 | 12/22/2005 | 12/22/2005 12:10:46 PM | P | PASS |
|
|
The related alarm permit is now finaled, fire life safety completed satisfactory.
|
FIR05-00266
| INSP-Final Inspection | 12/22/2005 | 12/22/2005 | 12/22/2005 12:09:14 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD02-01689
| FIRE-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 12:07:15 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 12/21/2005 at 2:42:42 PM. Contact: ###-####. Phone call to contractor to inform him there is no related fire inspection signature required or associated with this project, wrong inspection request called in.
|
FIR05-00659
| INSP-Sprinkler Rough-in/Hydro | 12/21/2005 | 12/22/2005 | 12/22/2005 12:04:45 PM | A | PART |
|
|
Overhead hydrostatic test of the antifreeze system passed. The supply main connection for this area has been changed significantly from the approved plans- system is now fed off the dead end main of the adjacent gridded wet system, not the 3" wet main from the warehouse as shown, need to resubmit plans for approval of this change, an overhead door has also been installed at the adjacent storage area requiring a sw to be installed.
|
FIR05-00743
| INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 11:38:31 AM | A | PASS |
|
|
Correction issue has been completed, fire sprinkler passed.
|
FIR05-00595
| INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 11:36:24 AM | A | PASS |
|
|
Resubmittals verified, duct detectors tested okay, fire alarm final inspection passed.
|
BLD05-00011
| FIRE-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 11:34:06 AM | A | PASS |
|
|
Fire life safety is acceptable, c/n items have been completed.
|
FIR05-00618
| INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 11:31:37 AM | A | PASS |
|
|
Fire alarm tested satisfactory, inspection passed.
|
FIR05-00236
| INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 8:48:32 AM | A | PASS |
|
|
Defficient issues have been corrected, inspection passed.
|
FIR05-00754
| INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 8:47:41 AM | A | PASS |
|
|
Defficient items have been corrected, inspection passed.
|
FIR05-00266
| INSP-Final Inspection | 12/22/2005 | 12/22/2005 | 12/22/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler passed final inspection, c/n items are complete.
|