Inspections for the day of: Thursday, December 22, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01911 FIRE-Final Inspection12/22/200512/22/200512/23/2005 8:29:31 AMPPART
###-#### Need to provide ADA approved hardware at the pocket door to the confrence room per IFC requirements, all other items tested okay.
BLD05-00978 FIRE-Final Inspection12/21/200512/22/200512/22/2005 4:35:04 PMAPART
On site confrence to discuss requirements for use approval at the separate covered loading dock structure.
FIR05-00738 INSP-Sprinkler Rough-in12/22/200512/22/200512/22/2005 3:41:09 PMPPART
UG fire supply line is acceptable to cover.
MIS05-00218 FIR-Final12/22/200512/22/200512/22/2005 3:21:01 PMPPASS
All c/n items have been completed, life safety passed inspection.
BLD05-01668 FIRE-Final Inspection12/22/200512/22/200512/22/2005 2:52:55 PMPPASS
Life safety for vanilla finish is satisfactory.
MIS05-00136 FIR-Final12/21/200512/22/200512/22/2005 2:45:55 PMAPASS
Life safety is acceptable, existing hardware on the main entry/exit doors is satisfactory per building plan reviewer Ron Hill.
BLD05-00458 BLD-Final12/22/200512/22/200512/22/2005 12:10:46 PMPPASS
The related alarm permit is now finaled, fire life safety completed satisfactory.
FIR05-00266 INSP-Final Inspection12/22/200512/22/200512/22/2005 12:09:14 PMPPASS
Fire sprinkler permit finaled.
BLD02-01689 FIRE-Final Inspection12/21/200512/22/200512/22/2005 12:07:15 PMACANC
Scheduled by a contractor via Hello! on 12/21/2005 at 2:42:42 PM. Contact: ###-####. Phone call to contractor to inform him there is no related fire inspection signature required or associated with this project, wrong inspection request called in.
FIR05-00659 INSP-Sprinkler Rough-in/Hydro12/21/200512/22/200512/22/2005 12:04:45 PMAPART
Overhead hydrostatic test of the antifreeze system passed. The supply main connection for this area has been changed significantly from the approved plans- system is now fed off the dead end main of the adjacent gridded wet system, not the 3" wet main from the warehouse as shown, need to resubmit plans for approval of this change, an overhead door has also been installed at the adjacent storage area requiring a sw to be installed.
FIR05-00743 INSP-Final Inspection12/21/200512/22/200512/22/2005 11:38:31 AMAPASS
Correction issue has been completed, fire sprinkler passed.
FIR05-00595 INSP-Final Inspection12/21/200512/22/200512/22/2005 11:36:24 AMAPASS
Resubmittals verified, duct detectors tested okay, fire alarm final inspection passed.
BLD05-00011 FIRE-Final Inspection12/21/200512/22/200512/22/2005 11:34:06 AMAPASS
Fire life safety is acceptable, c/n items have been completed.
FIR05-00618 INSP-Final Inspection12/21/200512/22/200512/22/2005 11:31:37 AMAPASS
Fire alarm tested satisfactory, inspection passed.
FIR05-00236 INSP-Final Inspection12/21/200512/22/200512/22/2005 8:48:32 AMAPASS
Defficient issues have been corrected, inspection passed.
FIR05-00754 INSP-Final Inspection12/21/200512/22/200512/22/2005 8:47:41 AMAPASS
Defficient items have been corrected, inspection passed.
FIR05-00266 INSP-Final Inspection12/22/200512/22/200512/22/2005 12:00:00 AMPPASS
Fire sprinkler passed final inspection, c/n items are complete.