PLM06-01864
| Final | 12/22/2006 | 12/22/2006 | 12/22/2006 3:30:41 PM | P | PASS |
|
|
2440; Phone #: ###-#### Internet Inspection Request from: Kim Alderson
|
PLM06-02280
| Final | 12/22/2006 | 12/22/2006 | 12/22/2006 2:15:58 PM | P | PASS |
|
|
this permit was for rough-in only.
|
PLM06-04067
| Final | 12/22/2006 | 12/22/2006 | 12/22/2006 2:14:26 PM | P | PASS |
|
|
###-#### tom-final ok with fixtures caulked-this permit was for trim only.
|
PLM06-01762
| Final | 12/21/2006 | 12/22/2006 | 12/22/2006 1:26:45 PM | A | PART |
|
|
Scheduled by a contractor via Hello! on 12/21/2006 at 3:53:02 PM. Contact: ###-####.need to install rpbp on dishwasher, hot & cold supply's for washer-need dbcv on ice machine-need pvb on eye wash or shortin hose to have 1" air gap-replace rpbp for steam unit-install all c/o plugs-need 1" air gap on t&p lines in mech room-cap drain line on future sink.
|
PLM06-01864
| Final | 12/21/2006 | 12/22/2006 | 12/22/2006 1:06:46 PM | A | CANC |
|
|
JOB #2440; Phone #: ###-#### Internet Inspection Request from: Kim Alderson
|
PLM06-03243
| Plumbing Rough-in | 12/21/2006 | 12/22/2006 | 12/22/2006 9:49:16 AM | A | FAIL |
|
|
re inspection; Phone #: ###-#### Internet Inspection Request from: Penny Smith-no more then 35 fixture units on a 3" horizontal drain, glue overhead cleanout plugs in, support dwv every 4'. ok to pull test.
|
PLM06-04020
| Plumbing Rough-in | 12/21/2006 | 12/22/2006 | 12/22/2006 8:44:03 AM | A | PASS |
|
|
Gene; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett
|