Inspections for the day of: Friday, December 22, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00615 INSP-Final Inspection12/21/200612/22/200612/26/2006 2:14:47 PMPFAIL
Project work is not ready for final as requested due to missing ceilings, ceiling tile, escutcheons, safety caps at some heads are not removed. The as-builts for system modifications made at the new stairway will not be accepted as the work performed exceeds the scope of changes allowed to be approved in the field. Submit documents showing modifications for plan review and approval prior to next inspection.
BLD06-01188 FIRE-Final Inspection12/22/200612/22/200612/26/2006 11:55:00 AMPPART
Corrections at the 2nd floor have been verified for completion, fire life safety is satisfactory for the second floor perimeter areas.
FIR06-00840 INSP-Final Inspection12/21/200612/22/200612/25/2006 11:32:22 PMPCANC
Inspection rescheduled for 12/26.
FIR06-00846 INSP-Sprinkler Rough-in12/22/200612/22/200612/22/2006 2:35:06 PMPPART
Overhead sprinkler rough-in is approved for cover at the drop ceiling areas.
BLD06-02366 FIRE-Final Inspection12/22/200612/22/200612/22/2006 1:26:58 PMPPASS
Fire life safety is satisfactory, inspection passed.
FIR06-00629 INSP-Final Inspection12/18/200612/22/200612/22/2006 1:26:02 PMPPASS
Fire sprinkler final inspection passed, permit finaled.
FIR06-00613 INSP-Final Inspection12/22/200612/22/200612/22/2006 1:25:21 PMPPASS
Fire alarm permit finaled.
BLD06-03218 FIRE-Final Inspection12/22/200612/22/200612/22/2006 11:07:06 AMPPASS
Corrections for the fire sprinkler system are complete, fire alarm work to replace the painted strobe appliance boxes pending, remainder of fire life safety passed inspection.
BLD06-01919 FIRE-Final Inspection12/22/200612/22/200612/22/2006 11:02:30 AMPPASS
Fire life safety for the vanilla shell passed inspection.
FIR06-00994 INSP-Final Inspection12/21/200612/22/200612/22/2006 10:44:34 AMAPASS
Fire sprinkler work passed field inspection, permit finaled.
FIR05-00271 INSP-Sprinkler Rough-in/Hydro12/20/200612/22/200612/22/2006 10:06:35 AMAPART
Approval for overhead fire sprinkler cover on the first and second floors of building #7 only. Third floor will require an inspeciton for cold cavity protection prior to cover.
FIR06-00910 INSP-Sprinkler Rough-in12/21/200612/22/200612/22/2006 10:04:04 AMAPART
Rough-in is okay for cover at the hard lid ceilings on the first and second floors only. Two heads at the 1st floor sushi bar soffit to be added and verified for compliance at the next scheduled inspection.