FIR08-00731
| INSP-Sprinkler Rough-in/Hydro | 12/22/2008 | 12/22/2008 | 12/22/2008 5:19:30 PM | P | PART |
|
|
See activity notes 12/9.
|
FIR08-00668
| INSP-Final Inspection | 12/19/2008 | 12/22/2008 | 12/22/2008 5:15:31 PM | P | PART |
|
|
Functional alarm testing passed however new device addresses and descriptors are not accurate, provide revised drawings and an updated map at the panel prior to final.
|
FIR08-00852
| INSP-Conference | 12/22/2008 | 12/22/2008 | 12/22/2008 5:13:06 PM | P | DONE |
|
|
On site conference regarding gas valve location.
|
BLD08-02505
| FIRE-Final Inspection | 12/22/2008 | 12/22/2008 | 12/22/2008 2:22:18 PM | P | PASS |
|
|
Fire life safety passed, fire extinguishers posted while on site.
|
FIR08-00732
| INSP-Final Inspection | 12/19/2008 | 12/22/2008 | 12/22/2008 2:21:14 PM | A | FAIL |
|
|
Three non-functional dampers at the 6th floor noted on plans include address 238, 230, and 239-vanes do not fully close, backward relay, motor failure. The 4th and 5th floors not yet tested.
|
BLD08-00999
| FIRE-Final Inspection | 12/19/2008 | 12/22/2008 | 12/22/2008 10:27:13 AM | A | DEFR |
|
|
Intended for structural final inspection, notified contractor.
|
BLD08-02547
| FIRE-Final Inspection | 12/19/2008 | 12/22/2008 | 12/22/2008 10:25:32 AM | A | FAIL |
|
|
Need to provide approved hardware at the main entry/exit doors for suite B and suite E as discussed and per building review notes.
|
FIR08-00504
| INSP-Sprinkler Rough-in/Hydro | 12/19/2008 | 12/22/2008 | 12/22/2008 8:23:29 AM | A | CANC |
|
|
Jared is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|