Inspections for the day of: Monday, December 22, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00731 INSP-Sprinkler Rough-in/Hydro12/22/200812/22/200812/22/2008 5:19:30 PMPPART
See activity notes 12/9.
FIR08-00668 INSP-Final Inspection12/19/200812/22/200812/22/2008 5:15:31 PMPPART
Functional alarm testing passed however new device addresses and descriptors are not accurate, provide revised drawings and an updated map at the panel prior to final.
FIR08-00852 INSP-Conference12/22/200812/22/200812/22/2008 5:13:06 PMPDONE
On site conference regarding gas valve location.
BLD08-02505 FIRE-Final Inspection12/22/200812/22/200812/22/2008 2:22:18 PMPPASS
Fire life safety passed, fire extinguishers posted while on site.
FIR08-00732 INSP-Final Inspection12/19/200812/22/200812/22/2008 2:21:14 PMAFAIL
Three non-functional dampers at the 6th floor noted on plans include address 238, 230, and 239-vanes do not fully close, backward relay, motor failure. The 4th and 5th floors not yet tested.
BLD08-00999 FIRE-Final Inspection12/19/200812/22/200812/22/2008 10:27:13 AMADEFR
Intended for structural final inspection, notified contractor.
BLD08-02547 FIRE-Final Inspection12/19/200812/22/200812/22/2008 10:25:32 AMAFAIL
Need to provide approved hardware at the main entry/exit doors for suite B and suite E as discussed and per building review notes.
FIR08-00504 INSP-Sprinkler Rough-in/Hydro12/19/200812/22/200812/22/2008 8:23:29 AMACANC
Jared is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus