Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02323 FIRE-Final Inspection12/22/201112/22/201112/23/2011 11:09:40 AMPPART
BLD11-01578 FIRE-Final Inspection12/22/201112/22/201112/23/2011 11:08:54 AMPFAIL
Field work does not match approved plans, door between the laundry and dry storage room has not been removed, door 103 is not installed, one hour rating at some locations including the new office and kitchen/corridor doors is not maintained per plan review notes and annotations, EM lighting at the common exit path from the board room and managers offices has been enclosed behind the new office wall.
FIR11-00571 INSP-Final Inspection12/22/201112/22/201112/22/2011 5:24:28 PMPPART
Verified correction items, completed forward flow, final pending control valve tampers.
FIR11-00676 INSP-Final Inspection12/22/201112/22/201112/22/2011 4:38:06 PMPFAIL
New tamper switches at the sprinkler DCVA failed to report.
FIR11-00638 INSP-Sprinkler Rough-in12/21/201112/22/201112/22/2011 1:39:38 PMAPART
Overhead rough-in passed with the exception of two pendent heads at the 2nd floor excersise room to be relocated due to ceiling fan obstructions. Inspection for cold cavity protection required prior to cover approval.
BLD11-01396 FIRE-Final Inspection12/21/201112/22/201112/22/2011 1:36:04 PMAFAIL
Correction items for fire life safety approvals include; exit door hardware at four locations, missing EM lighting at two areas, project related fire alarm and sprinkler permit finals.
FIR11-00534 INSP-Final Inspection12/21/201112/22/201112/22/2011 1:31:25 PMAPART
Final walkthrough completed including verification of previous C/N items, intermediate temp. heads at the unit heaters in the basement and missing DCVA support installed while on site, forward flow test passed. Final pending repair of the tamper switch at the PIV and project related fire alarm permit work for sprinkler monitoring.
FIR11-00533 INSP-Final Inspection12/22/201112/22/201112/22/2011 1:26:02 PMPNR
FIR11-00533 INSP-Alarm Testing12/21/201112/22/201112/22/2011 1:25:38 PMAFAIL
Yard post indicator tamper switch reported as a trouble open circut, plans do not match installation- noted five tamper switches and two flow switches have been added due to a PIV, antifreeze loop and DCVA not shown on plans, FACP has been relocated, floor control valves are now located in the riser room. Waterflow switch/outside bell repaired while on site. An approved plan modification will be necessary.
FIR11-00648 INSP-Final Inspection12/21/201112/22/201112/22/2011 9:09:05 AMAPASS
Fire alarm testing for phase 2 work completed acceptable, permit finaled.