Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00381 ELE-Aging Inspection12/22/201412/22/201412/24/2014 11:20:24 AM CANC
ELE12-02616 ELE-Aging Inspection12/22/201412/22/201412/22/2014 3:22:56 PM DONE
Waiting for contractor to schedule
ELE12-02592 ELE-Aging Inspection12/22/201412/22/201412/22/2014 3:17:20 PM DONE
Waiting for contractor to schedule
ELE14-02082 Electrical Rough-In12/22/201412/22/201412/22/2014 3:13:09 PMPPASS
eletrical service via phone with jason 12-22-14 blh// Mike Phone #: ###-#### Office walls and bath hard lids rough in ok cover
ELE14-02082 Permanent Service12/22/201412/22/201412/22/2014 3:11:55 PMPPASS
eletrical service via phone with jason 12-22-14 blh// Mike Phone #: ###-#### p/s u/g n ok
ELE14-02848 Final12/19/201412/22/201412/22/2014 2:19:28 PMPNR
Electrical Final. Tim. ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence Misc circuits yet to land and labelling
ELE14-03119 Final12/22/201412/22/201412/22/2014 1:38:46 PMPFAIL
Kenny Phone #: ###-#### BCC 4-05-32- Code violations not to be retained.
210.8 All 15 and 20 amp 120 volt receptical outlets located within 6' of sink or wash basin shall have GFCI protection.
406.3(D)- Grounding type receptical outlets installed on ungrounded circuits shall have GFCI protection or be changed to non-grounding type recepticals
ELE14-03507 Permanent Service12/22/201412/22/201412/22/2014 12:56:39 PMPPASS
Service change Phone #: ###-#### Inspection requested via web by cal crosby Hot tub and kitchen remodel in future to be permitted seperately. Check on final nipple to be solid conduit from meter to panel. Spoke to contractor he will change nipple prior to recconnect. p/s u/g rec ok
ELE14-03485 Electrical Rough-In12/19/201412/22/201412/22/2014 9:49:00 AMAPASS
Contact: Beau Cannon, wall rough-in please Phone #: ###-#### Inspection requested via web by Deb Gooden Misc walls in several offices altered. Rough in ok cover
ELE14-02930 Final12/20/201412/22/201412/22/2014 9:14:50 AMAPASS
call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
ELE14-03464 Rough-In Permanent Service12/19/201412/22/201412/22/2014 8:37:58 AMAPASS
Inspection requested via web by Lynn Solmon Rough in ok cover p/s u/g n ok