Inspections for the day of: Monday, December 22, 2014.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00725 INSP-Sprinkler Rough-in12/18/201412/19/2014 P 
The inspection is on the 4th floor. Mike S is your contact. Please call 1/2 hour prior to inspection Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00725 INSP-Sprinkler Rough-in12/19/201412/22/201412/22/2014 5:14:27 PMPPART
BLD14-02792 FIRE-Final Inspection12/22/201412/22/201412/22/2014 5:12:28 PMPPASS
Fire life safety inspection passed.
BLD14-02789 FIRE-Final Inspection12/22/201412/22/201412/22/2014 5:11:49 PMPPASS
Fire life safety inspection completed satisfactory.
BLD13-03291 FIRE-Conference12/22/201412/22/201412/22/2014 5:11:08 PMPDONE
Regarding project related fire alarm and sprinkler permit work.
FIR14-00885 INSP-Final Inspection12/22/201412/22/201412/22/2014 5:09:43 PMPPASS
Fire sprinkler work approved for final. Inspection passed.
FIR14-00261 INSP-Sprinkler Rough-in12/19/201412/22/201412/22/2014 5:08:40 PMPPART
OH work at the 1st, 2nd, 3rd and 4th floor corridors approved for cover. Need to provide vertical restraint at one armover and pendent 4th floor north end.
BLD14-00904 FIRE-Final Inspection12/22/201412/22/201412/22/2014 12:03:34 PMPPASS
Inspection passed. Fire life safety finaled.
FIR14-00377 INSP-Final Inspection12/19/201412/22/201412/22/2014 11:59:09 AMPPASS
Correction items and retest of the forward flow completed and passed. Fire sprinkler permit finaled.
FIR14-00470 INSP-Final Inspection12/19/201412/22/201412/22/2014 11:57:45 AMAFAIL
C/N items include; missing coverage at the shell space first floor near exit door, overspaced upright coverage at the 2nd floor west side, missing seismic bracing at the top of the 4" feed main 2nd floor, ceiling tile and escutcheons yet to be installed in some areas of the 1st floor, need finish pack at the riser, permit activity notes do not indicate a hydrostatic test for the OH or UG has been completed.
BLD14-01786 FIRE-Final Inspection12/15/201412/22/201412/22/2014 9:12:04 AMANR
Wendy (and Nicole ###-####) Phone #: ###-#### * Contact called and requested inspection be moved to 12/23 PM.
FIR13-00725 INSP-Sprinkler Rough-in/Hydro12/19/201412/22/201412/19/2014 9:58:52 AMPCANC
Inspection is on the 3rd floor. Mike S. is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus