FIR13-00725
| INSP-Sprinkler Rough-in | 12/18/2014 | 12/19/2014 | | P | |
|
|
The inspection is on the 4th floor. Mike S is your contact. Please call 1/2 hour prior to inspection Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
FIR13-00725
| INSP-Sprinkler Rough-in | 12/19/2014 | 12/22/2014 | 12/22/2014 5:14:27 PM | P | PART |
|
|
|
BLD14-02792
| FIRE-Final Inspection | 12/22/2014 | 12/22/2014 | 12/22/2014 5:12:28 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD14-02789
| FIRE-Final Inspection | 12/22/2014 | 12/22/2014 | 12/22/2014 5:11:49 PM | P | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
BLD13-03291
| FIRE-Conference | 12/22/2014 | 12/22/2014 | 12/22/2014 5:11:08 PM | P | DONE |
|
|
Regarding project related fire alarm and sprinkler permit work.
|
FIR14-00885
| INSP-Final Inspection | 12/22/2014 | 12/22/2014 | 12/22/2014 5:09:43 PM | P | PASS |
|
|
Fire sprinkler work approved for final. Inspection passed.
|
FIR14-00261
| INSP-Sprinkler Rough-in | 12/19/2014 | 12/22/2014 | 12/22/2014 5:08:40 PM | P | PART |
|
|
OH work at the 1st, 2nd, 3rd and 4th floor corridors approved for cover. Need to provide vertical restraint at one armover and pendent 4th floor north end.
|
BLD14-00904
| FIRE-Final Inspection | 12/22/2014 | 12/22/2014 | 12/22/2014 12:03:34 PM | P | PASS |
|
|
Inspection passed. Fire life safety finaled.
|
FIR14-00377
| INSP-Final Inspection | 12/19/2014 | 12/22/2014 | 12/22/2014 11:59:09 AM | P | PASS |
|
|
Correction items and retest of the forward flow completed and passed. Fire sprinkler permit finaled.
|
FIR14-00470
| INSP-Final Inspection | 12/19/2014 | 12/22/2014 | 12/22/2014 11:57:45 AM | A | FAIL |
|
|
C/N items include; missing coverage at the shell space first floor near exit door, overspaced upright coverage at the 2nd floor west side, missing seismic bracing at the top of the 4" feed main 2nd floor, ceiling tile and escutcheons yet to be installed in some areas of the 1st floor, need finish pack at the riser, permit activity notes do not indicate a hydrostatic test for the OH or UG has been completed.
|
BLD14-01786
| FIRE-Final Inspection | 12/15/2014 | 12/22/2014 | 12/22/2014 9:12:04 AM | A | NR |
|
|
Wendy (and Nicole ###-####) Phone #: ###-#### * Contact called and requested inspection be moved to 12/23 PM.
|
FIR13-00725
| INSP-Sprinkler Rough-in/Hydro | 12/19/2014 | 12/22/2014 | 12/19/2014 9:58:52 AM | P | CANC |
|
|
Inspection is on the 3rd floor. Mike S. is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|