FIR15-00618
| INSP-Alarm Testing | 12/18/2015 | 12/22/2015 | 12/22/2015 1:54:22 PM | P | DONE |
|
|
See the city approved plans for corridor detectors tested today. The fire doors did not release upon alarm of the corridor detectors, water flow switch did not function, elevator hat did not function. We tried to test some duct smoke detectors but the units would not turn on.
|
BLD15-04262
| FIRE-Final Inspection | 12/22/2015 | 12/22/2015 | 12/22/2015 1:49:48 PM | P | PASS |
|
|
life safety passed
|
FIR15-00687
| INSP-Sprinkler Rough-in | 12/21/2015 | 12/22/2015 | 12/22/2015 11:38:32 AM | A | PART |
|
|
2nd Floor has two rooms marked "ok" on the plans where the rough-in and tenting is passed and the piping can be covered. Except the piping for the balcony sidewalls has not been installed. This piping will need to be inspected prior to covering.
|
BLD15-04459
| FIRE-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 9:48:48 AM | A | FAIL |
|
|
Repair or remove the non-functional exit signs/emergency lights, provide annual inspection for the fire extinguishers, resubmit floor plans that matches actual layout, provide sticker at the main exit.
|
BLD15-01898
| FIRE-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 9:28:58 AM | A | PASS |
|
|
life safety passed
|
BLD15-04467
| FIRE-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 9:13:40 AM | A | PASS |
|
|
life safety passed
|
FIR15-00844
| INSP-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 8:56:48 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00618
| INSP-Alarm Testing | 12/17/2015 | 12/22/2015 | 12/18/2015 6:25:30 PM | A | CANC |
|
|
>> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|