FIR15-00824
| INSP-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 3:36:27 PM | P | PASS |
|
|
Final alarm/suppression system inspection passed/complete
|
FIR15-00701
| INSP-Sprinkler Rough-in/Hydro | 12/21/2015 | 12/22/2015 | 12/22/2015 3:22:11 PM | A | PASS |
|
|
200 psi hydrostatic test for 2 hours passed/complete for overhead fire sprinkler piping.
|
BLD15-04172
| FIRE-Final Inspection | 12/22/2015 | 12/22/2015 | 12/22/2015 1:44:55 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms. Tenant space has round type door knobs, mentioned to tenants that round type door knobs may need to be replaced. Front door had thumb-turn deadbolt, informed tenant that this should be changed to double key deadbolt, may be a difficult repair due to door age. Tenant is to mount one fire extinguisher upstairs and on fire extinguisher on main level, tenant has fire extinguishers. Life fire safety passed/complete.
|
BLD15-04444
| FIRE-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 11:07:10 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms. Thumb turn deadbolt located on south entry, tenant is going to have thumb-turn deadbolt removed. Front door, north entry has double key deadbolt and door to remain unlocked while occupied signage in place. Life fire safety passed/complete.
|
FIR15-00877
| INSP-Final Inspection | 12/21/2015 | 12/22/2015 | 12/22/2015 10:37:57 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|