Inspections for the day of: Friday, December 22, 2017.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03661 Final12/22/201712/22/201712/22/2017 2:46:24 PMPFAIL
call 30 min prior // Tom Phone #: ###-####
110.27- All NM cable below 8' from floor shall be protected from physical damage,
2 unfinished rooms, exposed to baseboard, exposed in kitchen cab for dishwasher.
Install spark rings for kitchen tile.
422.30- Disconnecting means shall be provided for water heater.
400.12- old existing flexible cords for penetrating walls and ceilings.
Devices shall be secured to boxes.
All covers shall be installed
ELE17-03842 Electrical Rough-In12/21/201712/22/201712/22/2017 1:46:18 PMAPASS
Curtis Phone #: ###-####
Exterior perimeter and exit lighting rough in ok cover
ELE17-04116 Electrical Rough-In12/21/201712/22/201712/22/2017 10:26:44 AMAPASS
Please inspect pool bond. Phone #: ###-#### Inspection requested via web by ERIC CENTERS
Pool bonds to equipment room, each end of cover, 4 corners with 2 on down hill corners rough in ok cover
ELE17-04295 Electrical Rough-In12/21/201712/22/201712/22/2017 9:13:01 AMAPASS
Kenny Phone #: ###-####
Detached garage, upstairs to be unfinished, garage rough in ok cover