ELE17-03122
| Final | 12/22/2017 | 12/22/2017 | 12/22/2017 2:16:33 PM | P | PASS |
|
|
This Is Ready For Final Pleaae Call Me ###-#### The Door Code Is 5063 Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett final ok
|
ELE17-02662
| Final | 12/21/2017 | 12/22/2017 | 12/22/2017 1:18:55 PM | P | NR |
|
|
Phone #: ###-#### Inspection requested via web by A.M.E. Office still landing wires in panel Not ready
|
ELE17-04131
| Electrical Rough-In | 12/22/2017 | 12/22/2017 | 12/22/2017 1:07:23 PM | P | PASS |
|
|
We need a ufer inspection. Dave is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker ufer only ok
|
ELE17-02467
| Final | 12/22/2017 | 12/22/2017 | 12/22/2017 12:48:59 PM | P | PART |
|
|
Occupancy for office. Thank you and Merry Christmas Phone #: ###-#### Inspection requested via web by Tom Jenkins Max A/C fuse 25amp. Garage GFCI receps. Check at final. Temp final ok
|
ELE17-00963
| Electrical Rough-In | 12/22/2017 | 12/22/2017 | 12/22/2017 12:35:00 PM | P | PASS |
|
|
rough in for AC units on back side of building Phone #: ###-#### Inspection requested via web by Todd Hall rough in ok
|
ELE17-02485
| Electrical Rough-In | 12/22/2017 | 12/22/2017 | 12/22/2017 12:33:48 PM | P | PASS |
|
|
rough in for AC units on back side of building Phone #: ###-#### Inspection requested via web by Todd Hall rough in ok
|
ELE17-03973
| Final | 12/21/2017 | 12/22/2017 | 12/22/2017 10:51:52 AM | P | NR |
|
|
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Christian Kilpatrick Spoke to electrician Wont be ready in time for a P.M final
|
ELE17-03973
| Electrical Rough-In | 12/20/2017 | 12/22/2017 | 12/22/2017 10:50:54 AM | A | PASS |
|
|
Pls contact Spencer (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Christian Kilpatrick Listing inspection only ok
|
ELE17-02801
| Final | 12/21/2017 | 12/22/2017 | 12/22/2017 10:20:25 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder 210.52A2 Wall spaces greater than2ft shall hve recep. (master bed under 3 gang). 210.51D At least 1 recep shall be installed within 36in of sink basin. Recep shall be on adjacent wall. ( Master vanity) Exposed romex on either side of fireplace needs safed off, put in j-boxes.
|
ELE17-03681
| Final | 12/21/2017 | 12/22/2017 | 12/22/2017 9:36:27 AM | A | NR |
|
|
Requested photos have been sent to ###-####. Kevin King can meet onsite to go over installation, please call to schedule ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Ryan King 310.15B3A Adjustment factors for mare than 3 current carrying conductors in coduit. Met Kevin onsite. Labeling of conduits ok. Varified attic wiring and UL listing of all rooftop equipment. Will correct conduit from main panel to subpanel and call for final.
|
ELE13-03475
| ELE-Aging Inspection | 12/22/2017 | 12/22/2017 | 12/22/2017 7:42:41 AM | | PASS |
|
|
Drove to house. No violations seen. Will final permit.
|
ELE13-03475
| Final | 12/22/2017 | 12/22/2017 | 12/22/2017 7:41:52 AM | P | PASS |
|
|
No violations present. Final ok
|