Inspections for the day of: Friday, December 22, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00217 INSP-Final Inspection12/22/201712/22/201712/22/2017 2:25:00 PMPPART
Partial final inspection complete for overhead fire sprinklers, permit for fire sprinklers can be finaled when fire alarm associated components are inspected and passed.
BLD17-00926 FIRE-Final Inspection12/21/201712/22/201712/22/2017 2:08:07 PMPCANC
South side gate opticon sensor tested okay with fire department, other gate was still being worked on, fire department was not able to test other sensor. Inspection request will need to be rescheduled when other sesnor can be tested. This inspection request is cancelled.
FIR17-00748 INSP-Sprinkler Rough-in12/21/201712/22/201712/22/2017 1:58:51 PMACANC
Inspection request will be rescheduled per conversation with Anthony Phone #: ###-####, this request is cancelled.
BLD17-00412 FIRE-Final Inspection12/21/201712/22/201712/22/2017 11:07:10 AMAPASS
Previously noted items have been repaired, final life fire safety inspection for office building complete.
BLD17-03676 FIRE-Final Inspection12/21/201712/22/201712/22/2017 10:44:24 AMAPASS
Final life fire safety inspection for area of work complete.
FIR17-00726 INSP-Supply line flush12/21/201712/22/201712/22/2017 10:21:15 AMADONE
Underground supply flush complete.
FIR17-00317 INSP-Sprinkler Rough-in/Hydro12/21/201712/22/201712/22/2017 9:33:18 AMAPART
Rough to cover inspection for level 3 overhead fire sprinkler piping complete (4th floor from ground level), level 3 approved for cover.
BLD17-03688 FIRE-Final Inspection12/21/201712/22/201712/22/2017 9:07:31 AMAPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher has current inspection tag and will be mounted in discussed location. Noted that space does have round type door hardware and thumbturn deadbolts that are outside area of work. Final life fire safety inspection for area of work complete.
FIR17-00715 INSP-Final Inspection12/21/201712/22/201712/22/2017 9:05:30 AMAPASS
Final fire sprinkler inspection for area of work complete.
BLD16-02905 FIRE-Final Inspection12/21/201712/22/201712/22/2017 8:24:21 AMAPASS
Final life fire safety inspection for area of work complete.
FIR17-00206 INSP-Sprinkler Rough-in12/21/201712/22/201712/21/2017 10:08:10 AMACANC
Jon Beazer is the contact for this inspection. He needs a rough-in for the 3rd floor. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus