Inspections for the day of: Tuesday, December 23, 2003.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00283 INSP-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAPASS
This is grants cell. Thank you and have a great holiday; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
FIR03-00775 INSP-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAFAIL
could not give a final due to no ceiling tile installed. But fire sprinklers and ok to cover 12/23/2003 9:29:19 AM
FIR03-00558 INSP-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAPART
Vault and two offices to the west are ok to cover 12/23/2003 10:40:30 AM
BLD02-01071 FIRE-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAPASS
fire alarm and fire life safety finaled 12/23/2003 11:01:24 AM
BLD02-02717 FIRE-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAPASS
fire alarm and fire life safety finaled 12/23/2003 11:01:36 AM
FIR03-00206 INSP-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission for use of the new church pending the completion of the existing church areas 12/23/2003 8:39:13 AM
BLD03-02251 BLD-Conference12/23/200312/23/200312/23/2003 12:00:00 AMADONE
Provide suite numbers, test the existing duct smoke detectors and provide fire extinguishers
FIR03-00274 INSP-Final Inspection12/23/200312/23/200312/23/2003 12:00:00 AMAPASS
FIR03-00775 INSP-Final Inspection12/23/200312/23/200312/23/2003 12:00:00 AMAPASS
FIR01-00124 INSP-Final Inspection12/23/200312/23/200312/23/2003 12:00:00 AMPFAIL
The Ames backflow preventor is having a surging problem which won't allow the flow switch to activate. Owner needs to provide verification that the building will be provided with minimum heating for the wet sprinkler system 12/23/2003 4:28:17 PM
FIR03-00775 INSP-Final Inspection12/23/200312/23/200312/23/2003 12:00:00 AMPPASS
fire sprinklers and fire life safety finaled 12/23/2003 11:44:47 AM
FIR03-00594 INSP-Sprinkler Rough-in/Hydro12/22/200312/23/200312/23/2003 12:00:00 AMPPASS
underground hydro test and the 24 hour air test on the dry pipe system is ok 12/23/2003 3:37:24 PM
BLD02-02454 FIRE-Final Inspection12/22/200312/23/200312/23/2003 12:00:00 AMPPART
A temporary occupancy was given with dave millers permission until the existing building is completed. Battery calcs, map, breaker locks and breaker box location. Existing building needs to be inspected 12/23/2003 1:23:58 PM
FIR03-00258 INSP-Alarm Testing12/22/200312/23/200312/23/2003 12:00:00 AMPPART
A temporary occupancy was given with dave millers permission until the existing building is completed. Battery calcs, map, breaker locks and breaker box location. Existing building needs to be inspected 12/23/2003 1:23:42 PM
BLD03-02261 FIRE-Final Inspection12/23/200312/23/200312/23/2003 12:00:00 AMPPASS
fire life safety finaled 12/23/2003 1:24:21 PM