Inspections for the day of: Friday, December 23, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04411 Rough-In Permanent Service12/22/200512/23/200512/23/2005 1:36:54 PMPFAIL
vivian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s ok see added p/s, cor. posted for r/i called BCC shall install all outside cans, complete all makeup inside and outside, 300.4 nail plates and 11/4" where required, high and low voltage cables
ELE05-04606 Rough-In Permanent Service12/23/200512/23/200512/23/2005 12:06:33 PMPPASS
ron ###-#### called protect romex within 6ft of attic access, remove low voltage from space for p/s r/i ok, p/s u/g new ok
ELE05-03440 Final12/22/200512/23/200512/23/2005 10:17:11 AMAFAIL
aaron; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
cor. posted to electrical and low voltage contractors, electrical 230.9&24(B) clearence of service drop by back deck, low voltage 110.26(F)(2) remove phone and tv cables from dedicated space below p/s called
ELE05-04258 Electrical Rough-In12/22/200512/23/200512/23/2005 9:23:49 AMAFAIL
lamar - no phone # Internet Inspection Request from: Letitia Mesa cor. met owner 210.12 afci for bed rms, 250.148 grd all metal boxes, 300.4 nail plates and 11/4",314.16 box fill, 300.14 6" free lenght, complete all makeup, 210.52(A) outlet spacing, 210.52(B&C) address wiring in kit. ,314.43 no screws or nails in plastic boxes,314.17 use approved connectors for romex, 240.24and BCC overcurrent devices higher than 6ft 7", update permit for work in 7rms not 2 rms, 10 days to correct violations , uncover all wiring covered before inspection, or power may be disconnected, if more violations created permit may be voided, and owner required to secure contractor staple romex within 8 or 12 inches of boxes, seal all unused KOs
ELE05-04411 Permanent Service12/23/200512/23/200512/23/2005 12:00:00 AMPPASS
vivian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
p/s u/g new ok