Inspections for the day of: Friday, December 23, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04605 Electrical Rough-In12/23/200512/23/200512/23/2005 3:39:09 PMPPASS
call 30 min prior to meet for access//tom falash; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called elect, said to add light sws before cover if they decide to. ric walls only
ELE05-03253 Final12/22/200512/23/200512/23/2005 2:36:17 PMPFAIL
Scheduled by a contractor via Hello! on 12/22/2005 at 2:00:09 PM. Contact: ###-####. called contr, left corr notice, 406.5 recpt faceplates shall cover opening and seat against mounting surface, 410.12 luminaire shall cover outlet box, 352.30 rnc shall be strapped within 3' of panel,110.26 sufficient access and working space shall be provided and maintained about elect equipment,110.26(A)(1)&(2) work space width and depth shall be provided, 250.104(A) metal water piping shall be bonded
ELE05-04024 Final12/22/200512/23/200512/23/2005 10:32:53 AMAPASS
For first thing in am if possible. Thanks!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok to final
ELE05-04598 Rough-In Permanent Service12/22/200512/23/200512/23/2005 9:56:37 AMAPASS
ron ###-#### ric ok, p/s, u/g, n, ok
ELE05-04603 Final12/22/200512/23/200512/23/2005 9:31:45 AMAPASS
darrell ###-####///call to meet for access 20-30 min ok to final
ELE05-04386 Electrical Rough-In12/22/200512/23/200512/23/2005 8:30:34 AMAPASS
Scheduled by a contractor via Hello! on 12/22/2005 at 1:17:08 PM. Contact: ###-####. ok to cover rest of clg
ELE05-04602 Final12/22/200512/23/200512/23/2005 8:22:02 AMANH
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr, left message, no access