FIR09-00619
| INSP-Final Inspection | 12/22/2009 | 12/23/2009 | 12/24/2009 4:19:29 PM | A | CANC |
|
|
Please call 30 minutes prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton
|
FIR09-00693
| INSP-Final Inspection | 12/22/2009 | 12/23/2009 | 12/24/2009 4:18:58 PM | A | CANC |
|
|
Overbooked
|
FIR09-00233
| INSP-Final Inspection | 12/23/2009 | 12/23/2009 | 12/23/2009 5:41:16 PM | P | FAIL |
|
|
Overspaced notification appliances at two rooms, missing notification device at one room, duct detector sample and vent tubes must be installed per mfg. cut sheet, gate valves at the sprinkler riser incorrectly reported at offsite monitoring as trouble conditions, outside bell repaired while on site. FACP phone lines, battery trouble, SD and MP at the panel tested okay.
|
BLD09-01906
| FIRE-Final Inspection | 12/23/2009 | 12/23/2009 | 12/23/2009 5:33:53 PM | P | PASS |
|
|
Fire life safety inspection passed after corrections made while on site including posting of the building address, max. occupant load sign provided, fire extinguishers attatched to the wall at locations indicated, signage at manual pulls for the two hood systems.
|
FIR09-00722
| INSP-Final Inspection | 12/22/2009 | 12/23/2009 | 12/23/2009 5:30:48 PM | A | PASS |
|
|
Hood suppression system operated correctly under test conditons.
|
FIR09-00657
| INSP-Sprinkler Rough-in | 12/22/2009 | 12/23/2009 | 12/23/2009 12:55:35 PM | A | PART |
|
|
Overhead modifications at the tenant remodel okayed for cover, noted minor field changes at one room and matched to existing heads at the common corridor are acceptable.
|
FIR09-00622
| INSP-Final Inspection | 12/18/2009 | 12/23/2009 | 12/23/2009 12:52:01 PM | A | FAIL |
|
|
Completed functional testing of duct detectors at office areas A and B, HVAC unit at the NW corner office area "A" failed to shut down (address 92), obstructed vent tubes at two locations repaired while on site, see plans for devices tested to date, discussed inspection schedule, noted some previous c/n items are incomplete.
|
BLD09-00824
| FIRE-Final Inspection | 12/21/2009 | 12/23/2009 | 12/23/2009 12:42:35 PM | A | FAIL |
|
|
Inspection intended for BLD09-00823- need to provide missing suite address numbers, repair the exit sign/EM light at the northwest man door, adjust closure at the new ADA restroom door, request correct permit number for final. Plans must match work completed for project BLD08-00824.
|