FIR14-00574
| INSP-Sprinkler Rough-in/Hydro | 12/22/2014 | 12/23/2014 | 12/23/2014 3:36:21 PM | P | PASS |
|
|
Not ready for hydro test but the tenting inspection passed and piping can be covered.
|
FIR14-00596
| INSP-Sprinkler Rough-in/Hydro | 12/22/2014 | 12/23/2014 | 12/23/2014 3:33:45 PM | P | PASS |
|
|
underground supply line from the stub out to just passed the new canopy is ok for cover
|
FIR14-00480
| INSP-Final Inspection | 12/23/2014 | 12/23/2014 | 12/23/2014 2:53:20 PM | P | PART |
|
|
A temporary for the fire alarm permit only is being given with scotts approval until the large Vesda system has been calibrated/inspected and the dust covers have been removed from all detectors.. Will need the NFPA record of completion forms as well.
|
NAF14-00028
| INSP-Sprinkler Rough-in | 12/22/2014 | 12/23/2014 | 12/23/2014 2:51:44 PM | A | FAIL |
|
|
Inspection turned into conference since the piping installed in the trench does not meet the minimum 4'6" bury requirement. Piping needs to be installed at the correct depth and inspected for approval to cover which will include thrust blocks.
|
FIR14-00907
| INSP-Final Inspection | 12/22/2014 | 12/23/2014 | 12/23/2014 12:33:37 PM | A | PASS |
|
|
Permit finaled
|
BLD14-03596
| FIRE-Final Inspection | 12/22/2014 | 12/23/2014 | 12/23/2014 10:16:09 AM | A | FAIL |
|
|
No approved plans on site, remove the thumbturn dead bolt (keyed is ok), provide sticker at door, provide correct address.
|
BLD14-03614
| FIRE-Final Inspection | 12/22/2014 | 12/23/2014 | 12/23/2014 9:24:14 AM | A | PASS |
|
|
life safety passed
|
BLD14-03158
| FIRE-Final Inspection | 12/22/2014 | 12/23/2014 | 12/23/2014 9:23:47 AM | A | PASS |
|
|
life safety passed
|
FIR14-00574
| INSP-Sprinkler Rough-in/Hydro | 12/22/2014 | 12/23/2014 | 12/22/2014 4:54:50 PM | P | CANC |
|
|
This is a tenting/OH Hydro inspection. Richard C is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
BLD39-00143
| FIRE-Supply Line Flush | 12/16/2014 | 12/23/2014 | 12/16/2014 9:00:51 AM | P | CANC |
|
|
>> Inspection requested via mobile web by test Inspection cancelled via mobile web on Tuesday, December 16, 2014.
|