Inspections for the day of: Tuesday, December 23, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00574 INSP-Sprinkler Rough-in/Hydro12/22/201412/23/201412/23/2014 3:36:21 PMPPASS
Not ready for hydro test but the tenting inspection passed and piping can be covered.
FIR14-00596 INSP-Sprinkler Rough-in/Hydro12/22/201412/23/201412/23/2014 3:33:45 PMPPASS
underground supply line from the stub out to just passed the new canopy is ok for cover
FIR14-00480 INSP-Final Inspection12/23/201412/23/201412/23/2014 2:53:20 PMPPART
A temporary for the fire alarm permit only is being given with scotts approval until the large Vesda system has been calibrated/inspected and the dust covers have been removed from all detectors.. Will need the NFPA record of completion forms as well.
NAF14-00028 INSP-Sprinkler Rough-in12/22/201412/23/201412/23/2014 2:51:44 PMAFAIL
Inspection turned into conference since the piping installed in the trench does not meet the minimum 4'6" bury requirement. Piping needs to be installed at the correct depth and inspected for approval to cover which will include thrust blocks.
FIR14-00907 INSP-Final Inspection12/22/201412/23/201412/23/2014 12:33:37 PMAPASS
Permit finaled
BLD14-03596 FIRE-Final Inspection12/22/201412/23/201412/23/2014 10:16:09 AMAFAIL
No approved plans on site, remove the thumbturn dead bolt (keyed is ok), provide sticker at door, provide correct address.
BLD14-03614 FIRE-Final Inspection12/22/201412/23/201412/23/2014 9:24:14 AMAPASS
life safety passed
BLD14-03158 FIRE-Final Inspection12/22/201412/23/201412/23/2014 9:23:47 AMAPASS
life safety passed
FIR14-00574 INSP-Sprinkler Rough-in/Hydro12/22/201412/23/201412/22/2014 4:54:50 PMPCANC
This is a tenting/OH Hydro inspection. Richard C is your contact. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD39-00143 FIRE-Supply Line Flush12/16/201412/23/201412/16/2014 9:00:51 AMPCANC
>> Inspection requested via mobile web by test Inspection cancelled via mobile web on Tuesday, December 16, 2014.