Inspections for the day of: Wednesday, December 23, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01900 ELE-Aging Inspection12/23/201512/23/201512/23/2015 2:51:20 PM DONE
Waiting on owner
ELE15-03819 Final12/23/201512/23/201512/23/2015 2:45:02 PMPFAIL
Call me in advance so I can bring prints and cutsheet. Thanks George Phone #: ###-#### Inspection requested via web by Thaniel Bishop
110,26- Work space shall be provided for solar disconnect 30" wide 36" deep.
300.14- A minimum of 6" free conductor shall be present at all junction points. UF from arrays to junction box.
ELE15-01812 Final12/22/201512/23/201512/23/2015 2:11:40 PMPFAIL
Phone #: ###-#### Inspection requested via web by William Salts
210.8- Roof top christmas receptacles on west side not working.
Bonding for solar support system shall be completed.
labels for solar service equipment shall be posted.
Verbal with Tate
ELE15-03599 Final12/23/201512/23/201512/23/2015 2:08:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3(B)- Dimmer in up bonus room shall have type of lamp suitable for this dimmer as per manufacturers instructions.
210.8- All garage 120 volt receptacles shall have GFCI protection. Garage GFI near panel not working.
300.15- All NM cables shall terminate in a box. 6-3 on back patio. 50 amp breaker turned on at time of inspection.
314.25- All boxes shall have covers or luminaire installed.
ELE15-04060 Rough-In Permanent Service12/23/201512/23/201512/23/2015 11:40:55 AMPPASS
Cal Phone #: ###-#### Rough in ok cover p/s u/g n ok Underground to service not connected due to placement will not work.
ELE15-03694 Electrical Rough-In12/22/201512/23/201512/23/2015 11:10:44 AMPCANC
Justin Hamby Phone #: ###-#### >> Inspection requested via web by Laurie Hoelscher Inspection cancelled from web by: Laurie Hoelscher
ELE15-04073 Final12/22/201512/23/201512/23/2015 10:20:07 AMAPASS
The Contractor and Home owner shall be there Phone #: ###-#### Inspection requested via web by Douglas Hackney This permit is for trim out only, rough in cover by permit ELE15-02436
Final ok
ELE15-02436 Final12/23/201512/23/201512/23/2015 9:53:00 AMPPASS
Job completed under permit ELE15-04073. Final ok
ELE15-04075 Electrical Rough-In12/22/201512/23/201512/23/2015 9:47:11 AMAPASS
Any questions call Allen, lock box 1049 Phone #: ###-#### Inspection requested via web by Neal Rumsey
Bath on left and dividing wall ceiling fished in rough in ok cover
ELE15-04078 Electrical Rough-In12/23/201512/23/201512/23/2015 9:08:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Kyle Lott
Walls and hard lid for bath and storage room rough in ok cover
ELE15-03427 Final12/22/201512/23/201512/23/2015 8:47:16 AMAPASS
###-#### Sign final ok