InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03841 Final12/24/200712/24/200712/24/2007 2:44:21 PMPCANC
steve Phone #: ###-#### wrong type request, see conference
ELE07-03841 Conference12/24/200712/24/200712/24/2007 1:25:55 PMPDONE
steve Phone #: ###-#### talked with owner, general about switching fireplace outlet and outside recpt too close to hot tub, told owner to work with electrical contractor
ELE07-03763 Final12/24/200712/24/200712/24/2007 1:02:21 PMPFAIL
mike - call for access Phone #: ###-#### called, left corr notice, nec 408.4 circuit directory shall be clear, concise, and explanatory, 300.11(A) raceways shall not be supported by grid, 348.28(A) fmc shall be supported within 12" oc raceway termination- hot water heater
ELE07-03763 Electrical Rough-In12/24/200712/24/200712/24/2007 12:26:25 PMPPASS
mike - call for access Phone #: ###-#### ok to cover ceiling only
ELE07-02398 Final12/21/200712/24/200712/24/2007 10:08:22 AMACANC
matt Phone #: ###-#### owner called, asked to cancel, not feeling well enough
ELE07-03252 Final12/21/200712/24/200712/24/2007 9:49:35 AMAFAIL
dean Phone #: ###-#### met owner, left corr notice, nec 334.15(B) nm cable shall be protected from physical damage with raceway, 422.30 shall provide disconnect for furnace, 404.9 faceplates for switches shall completely cover opening and seat against finished surface, 406.4 recpts shall be securely mounted in place, 406.4(D) receptacle faces shall be flush with or project from faceplates, 406.5 recpt faceplates shall completely cover opening and seat against mounting surface, 408.4 circuit directory shall be clear, concise, and evident for specific circuits,210.8 kitchen recpts shall be gfci protected-min 2 circuits, 210.12 bedrooms shall be protected by afci, 250.50 grounding electrode (water pipe) shall be used as grounding electrode,BCC all wiring shall be done and protected-range hood
ELE07-04118 Permanent Service12/21/200712/24/200712/24/2007 8:33:28 AMAPASS
Thank You Phone #: ###-#### Internet Inspection Request from: Tracy Robertson p/s, exst meter pak, n, ok