Inspections for the day of: Thursday, December 24, 2009.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00718 INSP-Final Inspection12/24/200912/24/200912/24/2009 4:18:30 PMPNR
Not ready for final per phone call from contractor.
BLD09-01427 FIRE-Conference12/24/200912/24/200912/24/2009 4:17:22 PMPDONE
On site conference regarding items needed for fire life safety approvals including door hardware at the second exit.
FIR09-00233 INSP-Final Inspection12/24/200912/24/200912/24/2009 4:16:14 PMPPASS
Correction items verified for completion, remainder of fire alarm work tested satisfactory, inspection passed, permit finaled.
FIR09-00622 INSP-Final Inspection12/23/200912/24/200912/24/2009 4:15:05 PMAPART
Completed duct detector testing at the production areas- see plan sheets areas E and F for annotations, incorrect sample tube orientation at address 16 repaired while on site.
FIR09-00572 INSP-Final Inspection12/23/200912/24/200912/24/2009 4:11:22 PMAPASS
Fire sprinkler final inspection passed, permit finaled.