Inspections for the day of: Tuesday, December 24, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02874 Final12/23/201312/24/201312/24/2013 12:52:48 PMPFAIL
Donald Phone #: ###-#### 408.4- Every circuit shall be legibly identified.
406.8(B)- 15 and 20 amp 120 volt receptical outlets installed outdoors shall be weather resistant type.
210.8- All 15 and 20 amp receptical outlets installed outside shall have GFCI protection.
110.3(B)- Devices not installed as per manufactureds instructions, GFI outlet lin/ load reversed, and reversed polarity, dead outlets.
210.8- receptical outlets installed to serve counter top in kitchen shall have GFCI protection.
314.25- All boxes shall have covers.
210.11(C)(3)- Bathroom recepticals shall be installed on a 20 amp circuit and shall not feed other outlets.
300.4- NM cable in garage shall not be secured less than 1 1/4" from framing surface.
340.12(10)- Type UF cable shall not be installed where subject to physical damage.
210.8- Garage 15 and 20 amp recepticals shall have GFCI protection.
MIS13-00336 ELE-Conference12/23/201312/24/201312/24/2013 10:48:15 AMADONE
report from inspector 411 doing electrical and plumbing work, no permit. Stopped by, sign on door wet floors, no answer at door
ELE13-03191 Final12/24/201312/24/201312/24/2013 10:33:35 AMPNR
Their asking for a ceiling inspection I''d like to final as much as possible I believe the building is ready thanks Brad Phone #: ###-#### >> Inspection requested via web by Brad Baker
ELE13-03191 Electrical Rough-In12/24/201312/24/201312/24/2013 10:31:16 AMPPASS
Their asking for a ceiling inspection I''d like to final as much as possible I believe the building is ready thanks Brad Phone #: ###-#### >> Inspection requested via web by Brad Baker Ceiling rough in ok cover
ELE13-03358 Final12/23/201312/24/201312/24/2013 10:14:16 AMAPASS
This will be for a final inspection. Please contact Justin Metcalf ###-#### before arrival to meet you there. Thank you and happy holidays Phone #: ###-#### >> Inspection requested via web by Laura Longshaw Final ok
ELE13-03389 Final12/23/201312/24/201312/24/2013 10:03:47 AMAPASS
THE WHIPS ARE INSTALLED. IM DONE COMPLETELY. Phone #: ###-#### >> Inspection requested via web by MARK PINNEY Final ok
ELE04-02374 Final12/24/201312/24/201312/24/2013 9:35:21 AMPPASS
Corrections completed on permit ele13-03542. Final ok
ELE13-03542 Final12/23/201312/24/201312/24/2013 9:33:40 AMAPASS
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden Corretions for ele04-02374 Final ok
ELE13-03358 Electrical Rough-In12/23/201312/24/201312/24/2013 9:16:29 AMAPASS
This will be a rough in inspection. Please contact Justin Metcalf ###-#### before arrival to meet you there. Thank you and have a great day Phone #: ###-#### >> Inspection requested via web by Laura Longshaw Rough in ok
ELE13-03519 Temporary Service12/23/201312/24/201312/23/2013 3:02:38 PMAPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Duplicate request t/s u/g n ok
ELE13-03519 Temporary Service12/23/201312/24/201312/23/2013 3:01:58 PMAPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s u/g n ok