Inspections for the day of: Wednesday, December 24, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02938 Final12/24/201412/24/201412/24/2014 12:22:44 PMPFAIL
Garage code 3283
Thank you and merry christmas Phone #: ###-#### Inspection requested via web by daniel bibikov
called contractor
422.11 overcurrent protection shall not exceed nameplate rating of appliance
334.12 NM shall not be used in damp or wet locations
422.31 Disconnecting means shall be provided for permanently installed appliances
ELE14-03505 Rough-In Permanent Service12/24/201412/24/201412/24/2014 11:06:54 AMACANC
Late morning if possible, thanks Phone #: ###-#### Inspection requested via web by Brad Girard
Wrong inspection, needed PS only
ELE14-03505 Permanent Service12/24/201412/24/201412/24/2014 11:06:47 AMPPASS
Late morning if possible, thanks Phone #: ###-#### Inspection requested via web by Brad Girard
PS, OH, N, OK
ELE12-00663 ELE-Aging Inspection12/24/201412/24/201412/24/2014 10:46:12 AM DONE
Stopped at home, owner let me make final inspection, final oK
ELE12-00663 Final12/24/201412/24/201412/24/2014 10:45:34 AMPPASS
Homeowner let me in to complete final inspection, Final oK
ELE14-03526 Final12/24/201412/24/201412/24/2014 10:28:01 AMPPASS
Phone #: ###-#### Inspection requested via web by michael hunt
Exterior meter main panel only. Final OK
ELE14-03526 Permanent Service12/23/201412/24/201412/24/2014 10:10:33 AMPPASS
Phone #: ###-#### Inspection requested via web by michael hunt
Exterior meter main only,
PS, OH, N, OK
ELE14-03478 Final12/23/201412/24/201412/24/2014 10:10:32 AMAPASS
Please call the homeowner Kam ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
corrections made, final OK
ELE14-01910 Electrical Rough-In12/23/201412/24/201412/24/2014 9:37:56 AMAFAIL
Garage rough in only

Tim is general contractor. Contact if needed

Phone #: ###-#### Inspection requested via web by John Harvey
left voicemail at number provided
334.30 NM shall be secured by staple, cable tie, strap, or similar fitting designed not to damage cable
3334.80 ampacity of nm, bundling of romex through holes, no more than six current carrying conductors allowed
250.68 A grounding electrode connection shall be accessible
300.4 NM through bored holes shall have protection where hole is less than 1 1/4 inch from framing member edge
352.24 Rigid PVC bends shall be made so conduit is not damaged
BCC, all items shall be ready for inspection type that is being made, there are romex and box hanging out of wall.
ELE14-02596 Final12/23/201412/24/201412/24/2014 8:44:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
corrections made, final oK
ELE14-03332 Final12/23/201412/24/201412/24/2014 8:31:17 AMACANC
Phone #: ###-#### Inspection requested via web by JENNY EMEL
wrong inspection requested, wanted perm service
ELE14-03332 Permanent Service12/24/201412/24/201412/24/2014 8:30:49 AMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL
PS, OH, N, OK