ELE14-02938
| Final | 12/24/2014 | 12/24/2014 | 12/24/2014 12:22:44 PM | P | FAIL |
|
|
Garage code 3283 Thank you and merry christmas Phone #: ###-#### Inspection requested via web by daniel bibikov called contractor 422.11 overcurrent protection shall not exceed nameplate rating of appliance 334.12 NM shall not be used in damp or wet locations 422.31 Disconnecting means shall be provided for permanently installed appliances
|
ELE14-03505
| Rough-In Permanent Service | 12/24/2014 | 12/24/2014 | 12/24/2014 11:06:54 AM | A | CANC |
|
|
Late morning if possible, thanks Phone #: ###-#### Inspection requested via web by Brad Girard Wrong inspection, needed PS only
|
ELE14-03505
| Permanent Service | 12/24/2014 | 12/24/2014 | 12/24/2014 11:06:47 AM | P | PASS |
|
|
Late morning if possible, thanks Phone #: ###-#### Inspection requested via web by Brad Girard PS, OH, N, OK
|
ELE12-00663
| ELE-Aging Inspection | 12/24/2014 | 12/24/2014 | 12/24/2014 10:46:12 AM | | DONE |
|
|
Stopped at home, owner let me make final inspection, final oK
|
ELE12-00663
| Final | 12/24/2014 | 12/24/2014 | 12/24/2014 10:45:34 AM | P | PASS |
|
|
Homeowner let me in to complete final inspection, Final oK
|
ELE14-03526
| Final | 12/24/2014 | 12/24/2014 | 12/24/2014 10:28:01 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by michael hunt Exterior meter main panel only. Final OK
|
ELE14-03526
| Permanent Service | 12/23/2014 | 12/24/2014 | 12/24/2014 10:10:33 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by michael hunt Exterior meter main only, PS, OH, N, OK
|
ELE14-03478
| Final | 12/23/2014 | 12/24/2014 | 12/24/2014 10:10:32 AM | A | PASS |
|
|
Please call the homeowner Kam ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan corrections made, final OK
|
ELE14-01910
| Electrical Rough-In | 12/23/2014 | 12/24/2014 | 12/24/2014 9:37:56 AM | A | FAIL |
|
|
Garage rough in only
Tim is general contractor. Contact if needed
Phone #: ###-#### Inspection requested via web by John Harvey left voicemail at number provided 334.30 NM shall be secured by staple, cable tie, strap, or similar fitting designed not to damage cable 3334.80 ampacity of nm, bundling of romex through holes, no more than six current carrying conductors allowed 250.68 A grounding electrode connection shall be accessible 300.4 NM through bored holes shall have protection where hole is less than 1 1/4 inch from framing member edge 352.24 Rigid PVC bends shall be made so conduit is not damaged BCC, all items shall be ready for inspection type that is being made, there are romex and box hanging out of wall.
|
ELE14-02596
| Final | 12/23/2014 | 12/24/2014 | 12/24/2014 8:44:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson corrections made, final oK
|
ELE14-03332
| Final | 12/23/2014 | 12/24/2014 | 12/24/2014 8:31:17 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL wrong inspection requested, wanted perm service
|
ELE14-03332
| Permanent Service | 12/24/2014 | 12/24/2014 | 12/24/2014 8:30:49 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL PS, OH, N, OK
|