Inspections for the day of: Thursday, December 26, 1996.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE96-02807 INSP - Permanent service12/26/199612/26/199612/26/1996 12:00:00 AM FAIL
/ / 315 - 53 failed there are some violations I could see, but the gar I could not do a complete inspection. Owner will call for reinspection
ELE96-04016 INSP - Permanent service12/26/199612/26/199612/26/1996 12:00:00 AM FAIL
/ / 315 - 53 failed cor. posted NEC, 250-91 can not splice GED in serv 250-83(c) drive grd rod flush with grade cor. posted in 200a panel
ELE96-04081 INSP - Permanent service12/26/199612/26/199612/26/1996 12:00:00 AM PASS
/ / 315 - 53 ok jf 200a o/h rec.
ELE96-04138 INSP - Permanent service12/26/199612/26/199612/26/1996 12:00:00 AM PASS
/ / 315 - 53 ok jf o/h new
ELE96-02807 INSP - Permanent service12/24/199612/26/199612/26/1996 12:00:00 AMAFAIL
12/26/96 315 - call steve on dig. pager ###-####/if not there he will me 53 failed cor. posted NEC,230-2 structure shall be served by one servic jf
ELE96-04081 INSP - Final12/24/199612/26/199612/26/1996 12:00:00 AMAPASS
12/26/96 315 - 53&14 ok jf
ELE96-03424 INSP - Final12/26/199612/26/199612/26/1996 12:00:00 AMPPASS
12/26/96 315 - 14 ok jf sur. posted 370-20 of NEC needs box extension mi this in the (am)
ELE96-03829 INSP - Electrical Rough-In12/26/199612/26/199612/26/1996 12:00:00 AMPPASS
12/26/96 315 - CEILING R/I 09 ok jf
ELE96-04016 INSP - Permanent service12/26/199612/26/199612/26/1996 12:00:00 AMPFAIL
12/26/96 315 - perm/service - and final early p.m. 53 failed see added and could final no power jf