Inspections for the day of: Wednesday, December 26, 2001.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00504 INSP-Sprinkler Rough-in/Hydro12/26/200112/26/200112/27/2001 12:00:00 AMPFAIL
###-#### slope of mains on south side on all floors not sloped back to east sides; air test started at 8:00 am for three risers on west wall of riser room - will return on 11/28 at 8 am 12/27/2001 1:08:29 PM
FIR01-00559 INSP-Alarm Testing12/19/200112/26/200112/26/2001 12:00:00 AMAPASS
###-#### CHRIS
BLD01-00445 FIRE-Conference12/21/200112/26/200112/26/2001 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 12/21/2001 at 11:04:11. Contact: ###-####. need address, hang extinguishers; 12/26/2001 8:25:36 AM
FIR01-00364 INSP-Final Inspection12/24/200112/26/200112/26/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 12/24/2001 at 08:14:46. Contact: ###-####. need occupancy separation heads complete; esctcheons; need calc sticker; bell sticker and test alarms 12/26/2001 1:23:49 PM
FIR99-00609 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 12/26/2001 6:53:20 AM
FIR99-00612 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 12/26/2001 6:53:44 AM
FIR99-00617 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 12/26/2001 6:54:09 AM
FIR99-00618 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 12/26/2001 6:54:39 AM
FIR99-00619 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 12/26/2001 6:55:01 AM
BLD01-02028 FIRE-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/26/2001 at 07:36:28. Contact: ###-####. need door to corridor with closure and hardware; occupant load sign 12/26/2001 4:56:43 PM
FIR01-00364 INSP-Sprinkler Rough-in/Hydro12/26/200112/26/200112/26/2001 12:00:00 AMPPART
Added by Inspector: 409 On 12/26/2001 1:24:10 PM hydro okay on dry standpipe
FIR01-00547 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 12/26/2001 4:54:08 PM
FIR01-00540 INSP-Final Inspection12/26/200112/26/200112/26/2001 12:00:00 AMPFAIL
Added by Inspector: 409 On 12/26/2001 4:56:16 PM need temporal tone; record of completion