FIR01-00504
| INSP-Sprinkler Rough-in/Hydro | 12/26/2001 | 12/26/2001 | 12/27/2001 12:00:00 AM | P | FAIL |
|
|
###-#### slope of mains on south side on all floors not sloped back to east sides; air test started at 8:00 am for three risers on west wall of riser room - will return on 11/28 at 8 am 12/27/2001 1:08:29 PM
|
FIR01-00559
| INSP-Alarm Testing | 12/19/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
###-#### CHRIS
|
BLD01-00445
| FIRE-Conference | 12/21/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 12/21/2001 at 11:04:11. Contact: ###-####. need address, hang extinguishers; 12/26/2001 8:25:36 AM
|
FIR01-00364
| INSP-Final Inspection | 12/24/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/24/2001 at 08:14:46. Contact: ###-####. need occupancy separation heads complete; esctcheons; need calc sticker; bell sticker and test alarms 12/26/2001 1:23:49 PM
|
FIR99-00609
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 6:53:20 AM
|
FIR99-00612
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 6:53:44 AM
|
FIR99-00617
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 6:54:09 AM
|
FIR99-00618
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 6:54:39 AM
|
FIR99-00619
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 6:55:01 AM
|
BLD01-02028
| FIRE-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/26/2001 at 07:36:28. Contact: ###-####. need door to corridor with closure and hardware; occupant load sign 12/26/2001 4:56:43 PM
|
FIR01-00364
| INSP-Sprinkler Rough-in/Hydro | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | P | PART |
|
|
Added by Inspector: 409 On 12/26/2001 1:24:10 PM hydro okay on dry standpipe
|
FIR01-00547
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 12/26/2001 4:54:08 PM
|
FIR01-00540
| INSP-Final Inspection | 12/26/2001 | 12/26/2001 | 12/26/2001 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 409 On 12/26/2001 4:56:16 PM need temporal tone; record of completion
|