ELE06-04490
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 4:49:18 PM | P | PASS |
|
|
steve ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-04128
| Electrical Rough-In | 12/26/2006 | 12/26/2006 | 12/26/2006 4:04:45 PM | P | PASS |
|
|
Skip; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ceiling ok to cover, left corr notice for other contr to move showroom repts to over window-see ele06-03880
|
ELE06-02633
| Final | 12/22/2006 | 12/26/2006 | 12/26/2006 4:02:32 PM | A | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, told contr to put in notes how to have access
|
ELE06-04093
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 3:19:44 PM | P | PASS |
|
|
Herald Note call ###-#### before insp ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
|
ELE06-03883
| Final | 12/22/2006 | 12/26/2006 | 12/26/2006 2:51:28 PM | P | PASS |
|
|
Cell # is ###-####, door is supposed to be open, if not there is a key in the closet outside the front door on the left hand side of the door jam on a nail and call for the garage code. Thanks; Phone #: ###-#### Internet Inspection Request from: Jamie Winters called, told contr to strap flex and move a/c lne from over top of panel, ok to final
|
ELE06-04693
| Electrical Rough-In | 12/26/2006 | 12/26/2006 | 12/26/2006 1:50:32 PM | P | PASS |
|
|
terry ###-#### ric ok, told to make-up 1 box and staple wire
|
ELE06-03668
| Electrical Rough-In | 12/26/2006 | 12/26/2006 | 12/26/2006 12:51:25 PM | P | PASS |
|
|
Jered; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett suggested contr use solid rather than stranded at ne pole base for ground, ok to cover
|
ELE06-03113
| Final | 12/22/2006 | 12/26/2006 | 12/26/2006 12:49:49 PM | P | PASS |
|
|
Thank you; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final
|
ELE06-04686
| Electrical Rough-In | 12/22/2006 | 12/26/2006 | 12/26/2006 10:19:42 AM | A | NR |
|
|
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called contr, all tile up, can't see for ri, told contr to call when he can show what done
|
ELE06-04690
| Electrical Rough-In | 12/22/2006 | 12/26/2006 | 12/26/2006 9:55:24 AM | A | FAIL |
|
|
robert-- ###-#### called left corr notice nec 200.6(A) grounded conductor 6 awg or smaller shall be identified by white or gray or 3 continuous white stripes along entire length, 250.119(A) insulated ground shall be green or have green with yellow stripes for id, 300.4(A)&(D) edge of holes and cable shall be 1 1/4" from edge of framing member
|
ELE06-03588
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 9:21:43 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE06-03602
| ELE-Aging Inspection | 12/26/2006 | 12/26/2006 | 12/26/2006 8:32:13 AM | | DONE |
|
|
see final
|
ELE06-03602
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 8:31:54 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE06-03601
| ELE-Aging Inspection | 12/26/2006 | 12/26/2006 | 12/26/2006 8:29:43 AM | | DONE |
|
|
see final
|
ELE06-03601
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 8:29:19 AM | A | PASS |
|
|
looked at sign, ok to final
|
ELE06-03589
| Final | 12/26/2006 | 12/26/2006 | 12/26/2006 8:27:53 AM | A | PASS |
|
|
looked at sign, ok to final
|