Inspections for the day of: Tuesday, December 26, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04490 Final12/26/200612/26/200612/26/2006 4:49:18 PMPPASS
steve ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-04128 Electrical Rough-In12/26/200612/26/200612/26/2006 4:04:45 PMPPASS
Skip; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ceiling ok to cover, left corr notice for other contr to move showroom repts to over window-see ele06-03880
ELE06-02633 Final12/22/200612/26/200612/26/2006 4:02:32 PMANH
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, told contr to put in notes how to have access
ELE06-04093 Final12/26/200612/26/200612/26/2006 3:19:44 PMPPASS
Herald Note call ###-#### before insp ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
ELE06-03883 Final12/22/200612/26/200612/26/2006 2:51:28 PMPPASS
Cell # is ###-####, door is supposed to be open, if not there is a key in the closet outside the front door on the left hand side of the door jam on a nail and call for the garage code. Thanks; Phone #: ###-#### Internet Inspection Request from: Jamie Winters called, told contr to strap flex and move a/c lne from over top of panel, ok to final
ELE06-04693 Electrical Rough-In12/26/200612/26/200612/26/2006 1:50:32 PMPPASS
terry ###-#### ric ok, told to make-up 1 box and staple wire
ELE06-03668 Electrical Rough-In12/26/200612/26/200612/26/2006 12:51:25 PMPPASS
Jered; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett suggested contr use solid rather than stranded at ne pole base for ground, ok to cover
ELE06-03113 Final12/22/200612/26/200612/26/2006 12:49:49 PMPPASS
Thank you; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final
ELE06-04686 Electrical Rough-In12/22/200612/26/200612/26/2006 10:19:42 AMANR
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz called contr, all tile up, can't see for ri, told contr to call when he can show what done
ELE06-04690 Electrical Rough-In12/22/200612/26/200612/26/2006 9:55:24 AMAFAIL
robert-- ###-#### called left corr notice nec 200.6(A) grounded conductor 6 awg or smaller shall be identified by white or gray or 3 continuous white stripes along entire length, 250.119(A) insulated ground shall be green or have green with yellow stripes for id, 300.4(A)&(D) edge of holes and cable shall be 1 1/4" from edge of framing member
ELE06-03588 Final12/26/200612/26/200612/26/2006 9:21:43 AMAPASS
looked at sign, ok to final
ELE06-03602 ELE-Aging Inspection12/26/200612/26/200612/26/2006 8:32:13 AM DONE
see final
ELE06-03602 Final12/26/200612/26/200612/26/2006 8:31:54 AMAPASS
looked at sign, ok to final
ELE06-03601 ELE-Aging Inspection12/26/200612/26/200612/26/2006 8:29:43 AM DONE
see final
ELE06-03601 Final12/26/200612/26/200612/26/2006 8:29:19 AMAPASS
looked at sign, ok to final
ELE06-03589 Final12/26/200612/26/200612/26/2006 8:27:53 AMAPASS
looked at sign, ok to final