Inspections for the day of: Thursday, December 26, 2013.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01179 ELE-Aging Inspection12/26/201312/26/201312/27/2013 10:17:04 AM DONE
called to have contractor call for final
ELE13-02761 Final12/26/201312/26/201312/26/2013 2:48:03 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Robert Murray called, left correction notice, NEC 210.52(A)(1)(2) shall provide receptacle in or by doorway into mbr , 314.23 laundry receptacle shall be securely fastened
ELE13-02449 Final12/26/201312/26/201312/26/2013 1:01:00 PMPNR
Mike Phone #: ###-#### met contractor, shall verify 6' spacing for receptace into mbr, shall fix open ground rear gfci, shall install kitchen outlets after granite installed, shall install fan and stair light, shall install all pool equipment, shall not use leds in closet unless enclosed, Note: stair light listed ok, contractor will verify available fault current for service, shall provide gfci for pantry receptacles, shall tighten loose receptacle
ELE12-01384 DOC - Permit Expired12/26/201312/26/201312/26/2013 9:56:23 AMAPASS
see doc expired BLD12-01509
ELE13-02890 Electrical Rough-In12/26/201312/26/201312/26/2013 9:40:59 AMAPASS
3 front soffit cans for cover inspection in new soffit. Phone #: ###-#### >> Inspection requested via web by Clay Jackson ok cover soffit only
ELE13-02831 Final12/25/201312/26/201312/26/2013 8:55:31 AMAPASS
Garage code for duplex unit on left 1000E, Garage code for duplex unit on right 2000E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final