ELE12-01179
| ELE-Aging Inspection | 12/26/2013 | 12/26/2013 | 12/27/2013 10:17:04 AM | | DONE |
|
|
called to have contractor call for final
|
ELE13-02761
| Final | 12/26/2013 | 12/26/2013 | 12/26/2013 2:48:03 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Murray called, left correction notice, NEC 210.52(A)(1)(2) shall provide receptacle in or by doorway into mbr , 314.23 laundry receptacle shall be securely fastened
|
ELE13-02449
| Final | 12/26/2013 | 12/26/2013 | 12/26/2013 1:01:00 PM | P | NR |
|
|
Mike Phone #: ###-#### met contractor, shall verify 6' spacing for receptace into mbr, shall fix open ground rear gfci, shall install kitchen outlets after granite installed, shall install fan and stair light, shall install all pool equipment, shall not use leds in closet unless enclosed, Note: stair light listed ok, contractor will verify available fault current for service, shall provide gfci for pantry receptacles, shall tighten loose receptacle
|
ELE12-01384
| DOC - Permit Expired | 12/26/2013 | 12/26/2013 | 12/26/2013 9:56:23 AM | A | PASS |
|
|
see doc expired BLD12-01509
|
ELE13-02890
| Electrical Rough-In | 12/26/2013 | 12/26/2013 | 12/26/2013 9:40:59 AM | A | PASS |
|
|
3 front soffit cans for cover inspection in new soffit. Phone #: ###-#### >> Inspection requested via web by Clay Jackson ok cover soffit only
|
ELE13-02831
| Final | 12/25/2013 | 12/26/2013 | 12/26/2013 8:55:31 AM | A | PASS |
|
|
Garage code for duplex unit on left 1000E, Garage code for duplex unit on right 2000E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
|