Inspections for the day of: Friday, December 26, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03530 Rough-In Permanent Service12/26/201412/26/201412/26/2014 11:58:43 AMPFAIL
Please call Ben if any questions Phone #: ###-#### Inspection requested via web by Ben Archibald
called contractor
WUI zone, cans need 2 hour fire barrier in soffits
300.11 cables shall be secured in place, SER at panel held by piece of NM is out beyond drywall level
300.4 cable installed parallel to framing member shall be 1 1/4 inch from edge of framing member
BCC: all items ready for inspection, NM cable on south end of garage to w/p outlet is hanging from top plate.
ELE13-00432 ELE-Aging Inspection12/26/201412/26/201412/26/2014 9:22:41 AM DONE
Spoke to Larry, QEI will research permit and look to final this permit when doing an inspection along with other work being performed on this building.
ELE14-02950 Final12/24/201412/26/201412/26/2014 9:08:16 AMANH
Generator final. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Spoke to Danny. No access. The branch manager is the only one with access and has the day off.
ELE14-03414 Final12/24/201412/26/201412/26/2014 8:43:22 AMAPASS
Jadd Phone #: ###-####
corrections made, final OK
ELE14-01910 Electrical Rough-In12/24/201412/26/201412/26/2014 8:28:35 AMAPASS
corrections made, garage r/i ok to cover