FIR17-00748
| INSP-Sprinkler Rough-in | 12/26/2017 | 12/26/2017 | 12/26/2017 1:29:58 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
FIR17-00522
| INSP-Sprinkler Rough-in | 12/26/2017 | 12/26/2017 | 12/26/2017 1:17:14 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads located on levels 2 and 3 excluding the corridors complete, approved for cover.
|
FIR17-00505
| INSP-Final Inspection | 12/26/2017 | 12/26/2017 | 12/26/2017 11:47:41 AM | P | FAIL |
|
|
Fire bell needs to be relocated to be visible from the address side of the street. Irrigation needs to shut off when flow switch activates, system was not wired for irrigation isolation at time of inspection.
|
FIR17-00607
| INSP-Sprinkler Rough-in | 12/26/2017 | 12/26/2017 | 12/26/2017 10:48:09 AM | P | FAIL |
|
|
Provide fire sprinklers/piping for pendants in main lobby and area behind main lobby. Provide fire sprinkler next to commercial hood. Remove insulation that is caught on multiple heads in attic space.
|
BLD17-01446
| FIRE-Final Inspection | 12/22/2017 | 12/26/2017 | 12/26/2017 10:08:59 AM | A | PASS |
|
|
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR17-00701
| INSP-Final Inspection | 12/22/2017 | 12/26/2017 | 12/26/2017 10:07:44 AM | A | PASS |
|
|
Final fire sprinkler inspection complete
|
FIR17-00742
| INSP-Sprinkler Rough-in/Hydro | 12/26/2017 | 12/26/2017 | 12/26/2017 9:38:52 AM | P | PASS |
|
|
Rough to cover inspection complete for area of work, approved for cover.
|
FIR17-00713
| INSP-Final Inspection | 12/21/2017 | 12/26/2017 | 12/26/2017 9:13:30 AM | A | CANC |
|
|
Access could not be provided per conversation with Rick ###-####, this request is cancelled and will be rescheduled when access can be provided.
|
BLD17-04367
| FIRE-Final Inspection | 12/22/2017 | 12/26/2017 | 12/26/2017 9:10:12 AM | A | CANC |
|
|
Inspection request will be rescheduled to accomidate inspector schedule per conversation with point of contact, Troy Phone #: ###-####, this request is cancelled.
|