MEC19-05778
| Final | 12/26/2019 | 12/26/2019 | 12/26/2019 3:41:20 PM | P | PASS |
|
|
Jeff Phone #: ###-####- furnace only co ok
|
MEC19-04641
| Final | 12/19/2019 | 12/26/2019 | 12/26/2019 2:58:04 PM | P | FAIL |
|
|
Please call when you''re on your way.
Thank you, Phone #: ###-#### Inspection requested via web by Dan McFate- need 2nd drain ran to garage floor- need arma flex completed at coil- bubble wrap insulation on R/A needs 3/4" gap for R-6 has R4.2 now- fix and recall in inspection
|
MEC19-04640
| Final | 12/19/2019 | 12/26/2019 | 12/26/2019 2:55:18 PM | P | FAIL |
|
|
Please call when you''re on your way.
Thank you, Phone #: ###-#### Inspection requested via web by Dan McFate- bubble wrap insulation on R/A needs 3'4" air gap to meet R-6 whats installed only meets R4.2- fix and recall in when ready- Furnace gas piping and co ok
|
MEC19-05735
| Final | 12/23/2019 | 12/26/2019 | 12/26/2019 1:57:49 PM | P | NR |
|
|
Please call Chris on the way to ensure that they are done, ###-####, thanks! Phone #: ###-#### Inspection requested via web by Brett Shannon- will need flue test witnessed- still installing
|
MEC19-04791
| Final | 12/26/2019 | 12/26/2019 | 12/26/2019 1:16:05 PM | P | FAIL |
|
|
call for access // Dale Phone #: ###-#### 1- need uv protection on line set outside at condenser and level condenser pad 2- need to seal line set and gas piping exterior penetrations weather tight 3- need to witness flue test 4- need combustion air for furnace/wh closet 5- need to remove gas gauge at meter and plug off 6- need to firecaulk pvc flue from furnace and w/h b vent at ceiling in closet
left notice front of furnace
|
MEC19-05759
| Final | 12/23/2019 | 12/26/2019 | 12/26/2019 12:15:05 PM | P | PASS |
|
|
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- unit heater final ok
|
MEC19-04610
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 11:14:45 AM | A | FAIL |
|
|
Final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- b vent on tube heater needs 1" clearance to combustilbles thru roof, roofing membrane needs removed and pipe extend up 12" above roof and install storm collar- boiler exhaust flue need secured to hangers and one installed on wall for intake- went over onsite with general contractor- temp occupancy ok
|
MEC19-05765
| Final | 12/26/2019 | 12/26/2019 | 12/26/2019 10:09:02 AM | A | PASS |
|
|
Please call home owner when on way. ###-#### Phone #: ###-#### Inspection requested via web by max sanders- furnace a/c coil co locking caps ok
|
MEC19-05275
| Final | 12/19/2019 | 12/26/2019 | 12/26/2019 9:32:08 AM | A | FAIL |
|
|
Please call Andrew in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- mini split final ok- need electrical permit issued for new circuit for condenser outside to final this permit out
|
MEC19-05591
| Final | 12/20/2019 | 12/26/2019 | 12/26/2019 9:04:05 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin- need to secure by pass ducting with hanger- need to seal and insulaste bypass ducting- need to remove tape on plenum and patch hole with metal and reseal- recall in when ready
|
MEC19-04071
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:49:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
|
MEC19-04073
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:48:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to seal and fasten R/A in furnace closet
|
MEC19-04072
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:47:49 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to seal and fasten R/A in furnace closet
|
MEC19-04069
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:46:43 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
|
MEC19-04068
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:40:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
|
MEC19-04067
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:40:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to fasten and seal R/A plenum in furnace closet
|
MEC19-04070
| Final | 12/24/2019 | 12/26/2019 | 12/26/2019 8:39:23 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to fasten and seal R/A in furnace closet
|