Inspections for the day of: Thursday, December 26, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05778 Final12/26/201912/26/201912/26/2019 3:41:20 PMPPASS
Jeff Phone #: ###-####- furnace only co ok
MEC19-04641 Final12/19/201912/26/201912/26/2019 2:58:04 PMPFAIL
Please call when you''re on your way.

Thank you, Phone #: ###-#### Inspection requested via web by Dan McFate- need 2nd drain ran to garage floor- need arma flex completed at coil- bubble wrap insulation on R/A needs 3/4" gap for R-6 has R4.2 now- fix and recall in inspection
MEC19-04640 Final12/19/201912/26/201912/26/2019 2:55:18 PMPFAIL
Please call when you''re on your way.

Thank you, Phone #: ###-#### Inspection requested via web by Dan McFate- bubble wrap insulation on R/A needs 3'4" air gap to meet R-6 whats installed only meets R4.2- fix and recall in when ready- Furnace gas piping and co ok
MEC19-05735 Final12/23/201912/26/201912/26/2019 1:57:49 PMPNR
Please call Chris on the way to ensure that they are done, ###-####, thanks! Phone #: ###-#### Inspection requested via web by Brett Shannon- will need flue test witnessed- still installing
MEC19-04791 Final12/26/201912/26/201912/26/2019 1:16:05 PMPFAIL
call for access // Dale Phone #: ###-####
1- need uv protection on line set outside at condenser and level condenser pad
2- need to seal line set and gas piping exterior penetrations weather tight
3- need to witness flue test
4- need combustion air for furnace/wh closet
5- need to remove gas gauge at meter and plug off
6- need to firecaulk pvc flue from furnace and w/h b vent at ceiling in closet

left notice front of furnace
MEC19-05759 Final12/23/201912/26/201912/26/2019 12:15:05 PMPPASS
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- unit heater final ok
MEC19-04610 Final12/24/201912/26/201912/26/2019 11:14:45 AMAFAIL
Final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- b vent on tube heater needs 1" clearance to combustilbles thru roof, roofing membrane needs removed and pipe extend up 12" above roof and install storm collar- boiler exhaust flue need secured to hangers and one installed on wall for intake- went over onsite with general contractor- temp occupancy ok
MEC19-05765 Final12/26/201912/26/201912/26/2019 10:09:02 AMAPASS
Please call home owner when on way. ###-#### Phone #: ###-#### Inspection requested via web by max sanders- furnace a/c coil co locking caps ok
MEC19-05275 Final12/19/201912/26/201912/26/2019 9:32:08 AMAFAIL
Please call Andrew in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- mini split final ok- need electrical permit issued for new circuit for condenser outside to final this permit out
MEC19-05591 Final12/20/201912/26/201912/26/2019 9:04:05 AMAFAIL
Phone #: ###-#### Inspection requested via web by Denise Colin- need to secure by pass ducting with hanger- need to seal and insulaste bypass ducting- need to remove tape on plenum and patch hole with metal and reseal- recall in when ready
MEC19-04071 Final12/24/201912/26/201912/26/2019 8:49:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-04073 Final12/24/201912/26/201912/26/2019 8:48:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to seal and fasten R/A in furnace closet
MEC19-04072 Final12/24/201912/26/201912/26/2019 8:47:49 AMAFAIL
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to seal and fasten R/A in furnace closet
MEC19-04069 Final12/24/201912/26/201912/26/2019 8:46:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-04068 Final12/24/201912/26/201912/26/2019 8:40:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-04067 Final12/24/201912/26/201912/26/2019 8:40:01 AMAFAIL
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to fasten and seal R/A plenum in furnace closet
MEC19-04070 Final12/24/201912/26/201912/26/2019 8:39:23 AMAFAIL
Phone #: ###-#### Inspection requested via web by Konrad Swartz- need to fasten and seal R/A in furnace closet