ELE02-02740
| ELE-Aging Inspection | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | | FAIL |
|
|
called contractor stopped at job site cor. posted 250.122(B) eqiup grd shall be same size as phase conductors ,250.86 install bond bushing conduit at pole or replace with schedule 80 pvc, shall not use ss connector in place of chase nipple 12/27/2002 6:10:55 PM
|
ELE02-02751
| ELE-Aging Inspection | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | | PASS |
|
|
was done by 331 he forgot to fast final 12/27/2002 5:05:23 PM
|
ELE02-02997
| ELE-Aging Inspection | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | | PART |
|
|
called contractor they said they are going to do work on 01/02/03 and will call for inspection 12/27/2002 6:22:56 PM
|
ELE02-03951
| Rough-In Permanent Service | 12/24/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | A | FAIL |
|
|
###-#### cor. posted called 300.4 1 1/4 inches 110.14(A) one wire per terminal neutral bus 210.52(A&B) needs outlets right and left back door kit dinning area 12/27/2002 11:36:47 AM
|
ELE02-03651
| Electrical Rough-In | 12/26/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | A | FAIL |
|
|
dick; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung done it 12/26/02 in the pm 12/27/2002 1:44:27 PM
|
ELE02-03697
| Electrical Rough-In | 12/26/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | P | PART |
|
|
###-####
walls only 12/27/2002 1:44:47 PM
|
ELE02-02685
| Electrical Rough-In | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | P | PART |
|
|
###-#### ernest (voice pager) r/i rms 528,529 12/27/2002 4:21:51 PM
|
ELE02-03731
| Electrical Rough-In | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | P | PART |
|
|
###-#### barbara partial final electrical contractor wiring ok, but low voltage wiring failed correction posted on building permit numbers bld02-02931, and bld02-02669 this was a ceiling inspection not partial final support cables and use approved jboxes, conduit bodies, of fittings shall not cut hole in pvc conduit too enter or exit cables west side #150 ok for ceiling cover only 12/27/2002 3:18:57 PM
|
ELE02-03651
| Electrical Rough-In | 12/27/2002 | 12/27/2002 | 12/27/2002 12:00:00 AM | P | PART |
|
|
r/i for u/g ok $42.00 reinspection fee due per J Schmer contractor does not call for inspection , he calls inspector for inspections , this has happened 3 times 12/27/2002 4:58:01 PM
|