Inspections for the day of: Friday, December 27, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00044 FIR-Aging Inspection12/27/200212/27/20021/3/2003 12:00:00 AM PART
Talked to Dave Maxwell and he said they will schedule for next week for testing 1/3/2003 8:59:12 AM
FIR02-00463 INSP-Final Inspection12/27/200212/27/200212/27/2002 12:00:00 AMAFAIL
PIV full of water; need filter on duct detector outlet port; FACP mounted high on wall, either relocate or add steps; need lockout on FACP circuit breaker; need to have NFPA 72 when complete
BLD02-02336 FIRE-Final Inspection12/23/200212/27/200212/27/2002 12:00:00 AMAPASS
###-####
BLD01-02887 FIRE-Final Inspection12/26/200212/27/200212/27/2002 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Amy Lawson alarms not needed 12/27/2002 12:51:45 PM
BLD02-00031 FIRE-Final Inspection12/26/200212/27/200212/27/2002 12:00:00 AMAFAIL
###-#### dave tested alarms; see FIR02-00463 for corrections 12/27/2002 10:55:11 AM
FIR02-00462 INSP-Final Inspection12/27/200212/27/200212/27/2002 12:00:00 AMPPASS
FIR02-00463 INSP-Final Inspection12/27/200212/27/200212/27/2002 12:00:00 AMPPASS
BLD02-00031 FIRE-Final Inspection12/27/200212/27/200212/27/2002 12:00:00 AMPPASS