FIR06-00853
| INSP-Sprinkler Rough-in | 12/26/2006 | 12/27/2006 | 12/27/2006 4:18:25 PM | P | PASS |
|
|
Need vault cover and forward flush
|
BLD06-03193
| FIRE-Final Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 4:11:28 PM | P | PASS |
|
|
Life safety finaled
|
FIR06-00779
| INSP-Sprinkler Rough-in | 12/27/2006 | 12/27/2006 | 12/27/2006 3:35:27 PM | P | PASS |
|
|
The sprinkler piping located above the hard lid in the retail area is ok to cover
|
BLD06-00100
| FIRE-Final Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 3:03:45 PM | P | FAIL |
|
|
Three of the four door need adjusting for self closure, provide apartment numbers. The smoke detector in the east bedroom of the first floor north apartment does not sound clearly and I was unable to test the smoke detector in the vaulted ceiling of the second floor south apartment.
|
BLD06-03007
| FIRE-Final Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 2:04:56 PM | P | PASS |
|
|
life safety finaled
|
BLD05-02073
| FIRE-Conference | 12/26/2006 | 12/27/2006 | 12/27/2006 11:25:11 AM | A | DONE |
|
|
Contractor wanted to "turn over" several rooms to St. Als for use. I stated that I would not be ok with that because the egress corridor from these rooms would have an inoperative fire alarm system.
|
FIR06-00631
| FIR-Aging Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 11:22:55 AM | | NR |
|
|
work is in progress
|
BLD06-00169
| FIRE-Final Inspection | 12/26/2006 | 12/27/2006 | 12/27/2006 9:55:27 AM | A | PASS |
|
|
life safety finaled
|
BLD06-02180
| FIRE-Final Inspection | 12/26/2006 | 12/27/2006 | 12/27/2006 9:55:05 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00491
| INSP-Final Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 9:39:32 AM | P | CANC |
|
|
mike; Note: 11:00 amPhone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Patricia Smith
|
FIR06-00710
| INSP-Final Inspection | 12/26/2006 | 12/27/2006 | 12/27/2006 9:38:47 AM | A | CANC |
|
|
bryan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
FIR06-00710
| INSP-Sprinkler Rough-in/Hydro | 12/26/2006 | 12/27/2006 | 12/27/2006 9:38:18 AM | A | FAIL |
|
|
Hydro test failed due to new heads needing added. Atleast one head is needed on the east side of the riser room and another to provide column protection per Chapter 12. Provide flexible couplings for the 4" riser piping at the racks. I notified the general contractor that there can be no storage below the stairs or sprinkler protection will be required. Also there are many screws for the rack piping hangers that are not ran all the way into the supporting structure.
|