ELE07-00558
| Conference | 12/27/2007 | 12/27/2007 | 12/28/2007 2:38:25 PM | P | DONE |
|
|
eric Phone #: ###-#### met owner , talked about in-use covers, strapping risers, bond screw, outside gfci, kitchen gfci, dead receptacles, open neutrals, open grounds, closet lights, abandon wire not used, flush switch plates, heater disconnect,flex over nm cable, staple nm cable at heater area, finish install lights, switches, dead receptacles, afci for bedrooms, if move in, allow 3' clear space around walls for inspection, owner made list of items
|
ELE07-03763
| Final | 12/27/2007 | 12/27/2007 | 12/27/2007 3:21:05 PM | P | PASS |
|
|
mike Phone #: ###-#### ok to final, signed occupancy card
|
ELE07-03763
| Electrical Rough-In | 12/27/2007 | 12/27/2007 | 12/27/2007 3:02:13 PM | P | PASS |
|
|
mike Phone #: ###-#### corrections made, ok to cover ceiling
|
ELE07-04212
| Permanent Service | 12/27/2007 | 12/27/2007 | 12/27/2007 2:15:08 PM | P | PASS |
|
|
james Phone #: ###-#### met contractor, told them that they need to call for am inspection, they assuming ok for power to reconnect before full inspection. contractor did not start work until after 12:30 pm. p/s o/h rec ok
|
ELE07-00558
| Final | 12/26/2007 | 12/27/2007 | 12/27/2007 1:36:47 PM | P | CANC |
|
|
eric Phone #: ###-#### see conference
|
ELE07-03638
| Final | 12/27/2007 | 12/27/2007 | 12/27/2007 12:51:06 PM | P | PASS |
|
|
michael Phone #: ###-#### ok to final
|
ELE07-04185
| Final | 12/26/2007 | 12/27/2007 | 12/27/2007 10:59:06 AM | A | FAIL |
|
|
scott Phone #: ###-#### called contr, left correction notice, nec 408.4 circuit directory shall be clear, concise and explanatory for each circuit, 110.12(A) unused openings shall be closed in panel, 334.30 nm cable shall be stapled within 12" of box, 314.23(A) boxes shall be securely mounted, 314.25 boxes shall have cover installed
|
ELE07-04202
| Electrical Rough-In | 12/26/2007 | 12/27/2007 | 12/27/2007 9:54:01 AM | A | PASS |
|
|
jay Note: please call for access Phone #: ###-#### corrections made, ric ok
|
ELE07-04210
| Electrical Rough-In | 12/26/2007 | 12/27/2007 | 12/27/2007 9:20:53 AM | A | PASS |
|
|
Need Electrical Rough in Thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable ric ok
|
ELE07-04210
| Permanent Service | 12/27/2007 | 12/27/2007 | 12/27/2007 9:10:20 AM | A | PASS |
|
|
Need Electrical Rough in Thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable p/s u/g n ok
|
ELE07-03252
| Electrical Rough-In | 12/26/2007 | 12/27/2007 | 12/27/2007 8:42:07 AM | A | PASS |
|
|
mark Note: 1st thing is possible Phone #: ###-#### corrections made, ok to final
|