Inspections for the day of: Thursday, December 27, 2007.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02899 Extend Permit 180 days12/21/200712/21/2007 P 
FIR07-00102 INSP-Final Inspection12/27/200712/27/200712/28/2007 7:32:09 AMPPASS
Fire supply line permit finaled, see project related FIR permit for some activities regarding this case.
FIR07-00885 INSP-Sprinkler Rough-in12/26/200712/27/200712/28/2007 7:28:51 AMPFAIL
See approved plans for heads marked at some locations as missing, overspaced, or in need of addition.
BLD06-03180 FIRE-Final Inspection12/26/200712/27/200712/27/2007 2:37:41 PMAFAIL
Need to repair EM lights at four locations including the exit discharges, provide signage at the door to the FACP room, one missing PFE provided while on site, need to final project related fire alarm permit and recieve copies of NFPA 72 record of completion.
BLD07-01877 FIRE-Final Inspection12/26/200712/27/200712/27/2007 12:36:01 PMAPASS
Noted items in need of repair are finished, fire life safety inspection passed.
BLD07-02356 FIRE-Final Inspection12/26/200712/27/200712/27/2007 12:34:48 PMAFAIL
Need the project related fire alarm and sprinkler permits finaled prior to BLD life safety approval, noted items from the previous visit including hardware at the east exit door are corrected, EM lights and exit signage tested okay, job is not in condition for life safety final at this time.
FIR07-00950 INSP-Final Inspection12/26/200712/27/200712/27/2007 12:31:09 PMAPASS
C/N items are completed and verified for functionality, inspection passed, permit finaled.
FIR07-00943 INSP-Final Inspection12/26/200712/27/200712/27/2007 12:29:53 PMAFAIL
Fire alarm initiation and notification devices functioned properly, however the overhead music system needs to shut down upon activation of the building fire alarm, remainder of testing passed.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro12/26/200712/27/200712/27/2007 12:26:05 PMAPART
OH hydrostatic testing for the 3rd floor SW quad passed, OH rough-in inspection also completed and okayed for cover as noted, two minor items repaired while on site, one head as annotated on plans to be relocated due to shadowing at an adjacent wall-can be verified at next scheduled visit.
FIR07-00957 INSP-Sprinkler Rough-in12/26/200712/27/200712/27/2007 12:22:00 PMAPART
On site conference regarding head spacing at one spray booth to avoid cold soldering, no other items reviewed or inspected today.