Inspections for the day of: Thursday, December 27, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-04211 Electrical Rough-In12/27/200712/27/200712/27/2007 4:40:07 PMPPASS
please call me for access I will need some lead time to meet you Thanks Shaun ###-#### Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ok cover ri
ELE07-04067 Final12/27/200712/27/200712/27/2007 3:54:45 PMPPASS
mitch Phone #: ###-#### ok final
ELE07-04206 Rough-In Permanent Service12/27/200712/27/200712/27/2007 2:36:59 PMPPART
** Re-Inspection Rough in Electrial - Walls
Take/Bake Pizzeria in Store
Rick @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kelly Felin ok cover walls only note ceiling needs to be cleaned up where we can see there is no service sub panel ready yet
ELE07-04177 Permanent Service12/27/200712/27/200712/27/2007 12:39:11 PMPPASS
100amp service upgrade, ready in afternoon for inspection to get power back on. Any questions call George @###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h n ok note they to call for final & we can look service
ELE07-04206 Electrical Rough-In12/26/200712/27/200712/27/2007 10:46:28 AMAFAIL
rick Phone #: ###-#### nec330.30(B) shall support mc cable within 12inch of box with approved supoorts. note t/w rick he needs to support emt in ceiling properly
ELE07-04168 Rough-In Permanent Service12/26/200712/27/200712/27/2007 10:25:08 AMAPASS
mike Phone #: ###-#### ok cover ri p/s u/g n ok
ELE07-03383 Final12/26/200712/27/200712/27/2007 10:24:36 AMAPASS
Mike, this is my blanket permit. Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok final
ELE07-01598 Electrical Rough-In12/26/200712/27/200712/27/2007 10:24:08 AMACANC
Scheduled by a contractor via Hello! on 12/26/2007 at 1:52:09 PM. wrong permit number
ELE07-00733 Electrical Rough-In12/27/200712/27/200712/27/2007 10:23:12 AMAPASS
ok cover light potting
ELE07-04102 Final12/26/200712/27/200712/27/2007 10:21:33 AMAPASS
brian - reinspection Phone #: ###-#### ok final corrections made